Jump to main content.


 Wellman, Texas (Round 2)

 
Site Information
Location: Wellman, TX
Population: 247
Address: Wellman Water Systems Center
P.O. Box 124
Wellman, TX
Contact: Marvin Crutcher, Operator (806) 637-6785
Demonstration Site: Wellman Water Systems
Enclosed Space: 60
Source Water: Ground Water
Maximum Daily Flow: 85 gpm
Existing Treatment: Chlorination
Arsenic Removal Technology: AdEdge Iron Media AD33 with pH Adjusted
Disposal Option: Lagoon

 

Project Status
Cooperative Research and Development Agreement (CRADA) signed Completed
CRADA approved by legal Completed
EPA/contractor site visit Completed
Contractor/system agreement Completed
Plans submitted Completed
Plans approved Completed
Equipment installed Completed
Study began Completed
Study completed Completed
Six-month report cleared N/A
Final report cleared N/A

 

Source Water Quality
Analysis mg/L Analysis mg/L
Total As 0.039, 0.033* pH - Units 7.75
As (III) N/A Ca 64, 58*
As (V) N/A Mg 60, 61*
Fe 0.024, 0.055* Na 107, 172*
Mn 0.006, <0.0004 Chloride 102, 131*
PO4 - P 0.096* Hardness as CaCO3 406
SiO2 19.5* T. Alkalinity as CaCO3 246, 302*
SO4 217, 224* TOC N/A

Note: All data provided by utility except as noted.
N/A = Not available
* = Data provided by EPA

Technical Contact:

Tom Sorg (513) 569-7370

See Also:

Wellman, TX Fact Sheet (PDF) (2 pp, 58 KB) June 2006

Federal Register Notice: Arsenic Treatment Demonstrations

Demonstration Program Participation

Demo Site Information Form (PDF) (2 pp, 57 KB)

Publications on Arsenic

Frequently Asked Questions


Local Navigation