Table 1.0 Operating Parameters of the Distribution System Simulator (508 Compliant)
Row 1
Parameter: Distribution System Simulator
Normal Operation: Parallel (6 individual Distribution
System Simulators)
Experimental Test Conditions: Parallel or Series
in groups of 6, 3, 2, or 1
Row 2
Parameter: Housing
Normal Operation: Ductile Iron (Non-lined)
Experimental Test Conditions: Ductile Iron (Non-lined)
Row 3
Parameter: Flow
Normal Operation: 88 g.p.m. or 1 ft/sec
Experimental Test Conditions: No Flow to 140 g.p.m. or
0 to 1.6 ft/sec
Row 4:
Parameter: Temperature
Normal Operation: 60 o F (15.5 o
C)
Experimental Test Conditions: 35 o F (1.6
o C) to Ambient
Row 5
Parameter: Chemical Control
Normal Operation: Free Chlorine 1.0 ppm
Experimental Test Conditions: Chemical control as needed
Row 6
Parameter: pH
Normal Operation: 7.0 to 7.5
Experimental Test Conditions: Control/monitor as needed
Row 7
Parameter: Turbidity
Normal Operation: < 0.5 NTU
Experimental Test Conditions: Control/monitor as needed
Row 8
Parameter: Water Supply
Normal Operation: Cincinnati - Tap water (Chlorinated)
Experimental Test Conditions: Dechlorinated, Deionized,
Tanked, Surface Water (River)