Jump to main content.


Vol. 57 No. 238 Thursday, December 10, 1992  p 58644 (Proposed Rule
    1/6187  


ENVIRONMENTAL PROTECTION AGENCY


40 CFR Part 82


[FRL-4542-9]


Protection of Stratospheric Ozone; Refrigerant Recycling


AGENCY: Environmental Protection Agency.


ACTION: Proposed Rule.


____________________________________________________________


SUMMARY: In this document, EPA proposes regulations under section 


608 of the Clean Air Act (the Act) that would establish a recycling



program for ozone depleting refrigerants recovered during the 


servicing and disposal of air conditioning or refrigeration 


equipment. The proposed regulations would require persons servicing



air conditioning and refrigeration equipment to observe certain 


service practices that reduce refrigerant emissions and would 


establish equipment and off-site reclaimer certification programs. 


In addition, EPA would require that ozone depleting compounds 


contained "in bulk" in appliances be removed prior to disposal 


of the appliances, and that all air conditioning and refrigeration 


equipment, except for small appliances and room air conditioners, 


be provided with a servicing aperture that would facilitate 


recovery of the refrigerant. These proposed regulations should 


significantly reduce emissions of ozone depleting refrigerants 


and therefore aid U.S. and global efforts to minimize damage 


to the ozone layer.


DATES: Written comments on the proposed rule must be received 


on or before January 22, 1993. A public hearing is scheduled 


for December 23, 1992 in the EPA Auditorium, located at 401 


M St., SW., Washington, DC.


ADDRESSES: Comments should be submitted in duplicate to the 


attention of Air Docket No. A-92--01 at: U.S. Environmental 


Protection Agency, 401 M Street, SW., Washington, DC 20460. 


The Public Docket is located in room M-1500, Waterside Mall 


(Ground Floor), U.S. Environmental Protection Agency, 401 M 


Street, SW., Washington, DC. Dockets may be inspected from 8 


a.m. until 12 noon, and from 1:30 p.m. until 3 p.m., Monday 


through Friday. A reasonable fee may be charged for copying 


docket materials.


FOR FURTHER INFORMATION CONTACT: Debbie Ottinger, Stratospheric 


Ozone Protection Branch, Global Change Division, Office of
Atmospheric 


and Indoor Air Programs, Office of Air and Radiation, ANR-445, 


401 M Street SW., Washington DC 20460. (202) 233-9200. The
Stratospheric 


Ozone Information Hotline at 1-800-296-1996 can also be contacted 


for further information on weekdays from 10:00 to 4:00, Eastern 


Time.


SUPPLEMENTARY INFORMATION: The contents of today's preamble 


are listed in the following outline:


I. Background


  A. Ozone Depletion


  B. Montreal Protocol and EPA's Implementing Regulations


  C. Excise Tax


  D. London Amendments to the Protocol


  E. Advance Notice of Proposed Rulemaking Regarding Recycling


  F. Clean Air Act Amendments of 1990


II. Section 608 of the Clean Air Act


III. Today's Proposed Rule


  A. Equipment Affected


  B. Factors Considered in the Development of this Proposal


  C. Overview of Proposed Requirements


  D. Public Participation


  E. Definitions and Interpretations


  F. Required Practices


  1. Evacuation of air conditioning and refrigeration equipment


  2. Leak repair


  3. Disposition of Recovered Refrigerant


  4. RCRA Regulations Regarding the Management of CFCs and CFC-


    Contaminated Wastes


  5. Handling Multiple Refrigerants in Recycling and Recovery 


    Equipment


  G. Certification of Recycling and Recovery Equipment


  1. Standards for recovery and recycling machines intended 


    for use with air conditioning and refrigeration equipment 


    except small appliances


  a. Recovery efficiency


  b. Refrigerant recovery rates


  c. Low loss fittings


  d. Purge loss


  e. Volume-sensitive shut-off


  2. Standards for recovery machines intended for use with small 


    appliances


  3. Possible standards for recycling and recovery machines 


    used with equipment identical to MVACs


  4. Testing of recycling and recovery equipment intended for 


    use on air conditioning and refrigeration equipment except 


    small appliances


  5. Testing of recycling and recovery equipment intended for 


    use on small appliances


  6. Effective Dates and Grand Fathering Provisions


  H. EPA Promotion of Service Technician Competence


  1. Curriculum or Test Content


  2. Administration


  3. Possible Need for Mandatory Certification


  I. Certification by Owners of Recycling or Recovery of Equipment


  J. Certification of Reclaimers


  K. Recordkeeping Requirements


  L. Safe Disposal Requirements


  M. Servicing Apertures


  N. Possible exemption from regulatory requirements for
refrigerant 


    uses for which no high-efficiency recovery technology exists


IV. Possible Future Rulemakings to Implement Section 608


V. Summary of Supporting Analyses


  A. Regulatory Impact Analysis


  B. Regulatory Flexibility Analysis


  C. Paperwork Reduction Act


I. Background  





A. Ozone Depletion  


   The stratospheric ozone layer protects the earth from the 


penetration of harmful ultraviolet (UV-B) radiation. On the 


basis of scientific evidence, a national and international
consensus 


exists that certain man-made halocarbons, including
chlorofluorocarbons 


(CFCs), halons, carbon tetrachloride, and methyl chloroform, 


must be restricted because of the risk of depletion of the
stratospheric 


ozone layer through the release of chlorine and bromine. To 


the extent depletion occurs, penetration of UV-B radiation
increases, 


resulting in potential health and environmental harm including 


increased incidence of certain skin cancers and cataracts,
suppression 


of the immune system, damage to plants including crops and aquatic 


organisms, increased formation of ground-level ozone and increased 


weathering of outdoor plastics.  


   The original theory linking CFCs to ozone depletion was first 


proposed in 1974. Since then, the scientific community has made 


remarkable advances in understanding atmospheric processes
affecting 


stratospheric ozone science. Model predictions in the late 1980s 


suggested that continued use of CFCs would lead to substantial 


ozone depletion in the middle of the next century. Despite the 


sophistication of these models, scientists did not predict the 


extent of the decrease in stratospheric ozone over Antarctica 


that was first reported in 1985. This seasonal loss of ozone 


over the south pole became known as the "Antarctic Ozone hole". 


   More recent studies have continued to deepen concern over 


stratospheric ozone loss. In 1988, the results of an international 


assessment of ozone trends were published in the Executive Summary 


of the Ozone Trends Panel Report. In addition to the ozone hole, 


this report stated that analysis of total-column ozone data 


showed measurable downward trends from 1969 to 1988 of 3 to 


5 percent in the northern hemisphere in the winter. In early 


1991, new scientific evidence from satellite data indicated 


a year-round loss of stratospheric ozone over the northern mid-


latitudes during the past decade of 3 to 5 percent. This amount 


is 2 times greater than past studies suggested and has raised 


the concern that ozone depletion appears to be occurring faster 


than theoretical models had predicted. A scientific assessment 


published in October, 1991 showed for the first time stratospheric 


ozone depletion in summertime over the continental United States. 


Most recently, analyses of atmospheric chemistry in the northern 



hemisphere have indicated that an ozone hole similar to the 


one in the antarctic could appear in the arctic. These analyses 


also imply that ozone depletion at the northern mid-latitudes 


could accelerate.  


   A more detailed discussion of the background of the ozone 


depletion problem, the scientific evidence regarding the issue, 


and the health and environmental effects of ozone depletion 


can be found at 56 FR 49548 (September 30, 1991).  


B. Montreal Protocol and EPA's Implementing Regulations  


   In September 1987, the United States and 22 other countries 


signed the Montreal Protocol on Substances that Deplete the 


Ozone Layer (the Protocol). As originally drafted, the Protocol 


called for production and consumption of certain CFCs (CFC-11, 


12, 113, 114, 115) and halons (Halon-1211, -1301 and -2402) 


to be frozen at 1986 levels beginning July 1, 1989, and January 


1, 1992, respectively, and for the CFCs to be reduced to 50 


percent of 1986 levels by 1998. To date, 76 nations representing 


well over 90% of the world's production capacity for CFCs and 


halons have signed the Montreal Protocol. EPA promulgated
regulations 


implementing the requirements of the 1987 Protocol through a 


system of tradeable allowances. EPA apportioned the allowances 


to producers and importers of ozone depleting substances
(controlled 


substances) based on their 1986 level of production and
importation. 


It then reduced the allowances for the controlled substances 


according to the schedule specified in the Protocol. (See 56 


FR 49548 (September 30, 1991) for a more detailed discussion 


of the Protocol and EPA's regulations to implement the phaseout 


of ozone-depleting substances.)  


C. Excise Tax  


   As part of the Omnibus Budget Reconciliation Act of 1989, 


the U.S. Congress levied an excise tax on the sale of CFCs and 


other chemicals that deplete the ozone layer, with specific 


exemptions for exports and recycling. The tax has operated as 


a complement to EPA's regulations limiting production and
consumption 


by increasing the costs of using virgin controlled substances. 


As a result of the tax, there is an added incentive for industry 


to shift away from controlled substances and to increase recycling 


activities. The tax has also stimulated the market for alternative 


chemicals and processes. The original excise tax was amended 


in 1991 to include methyl chloroform, carbon tetrachloride and 


other CFCs regulated by the amended Montreal Protocol and title 


VI of the Clean Air Act.  


D. London Amendments to the Protocol  


   Since the signing of the Protocol in 1987, additional scientific



evidence became available indicating that depletion of the
stratospheric 


ozone layer was occurring more quickly than had been anticipated. 


In response to this evidence (i.e. the 1988 Ozone Trends Panel 


Report), the Parties to the Protocol at their meeting in London 


in June 1990 amended the Protocol schedule for CFCs and halons 


to require a complete phaseout by January 1, 2000. Methyl
chloroform 


and carbon tetrachloride were added to the list of ozone depleting 


substances, with carbon tetrachloride phased out by January 


1, 2000 and methyl chloroform phased out by January 1, 2005. 


   The parties also passed a non-binding resolution regarding 


the use of hydrochlorofluorocarbons (HCFCs). HCFCs have been 


identified as interim substitutes for CFCs because they add 


much less chlorine to the stratosphere than fully halogenated 


CFCs. The Parties were concerned, however, that rapid growth 


in the amount of use of these chemicals over time would still 


pose a threat to the ozone layer. As a result, the resolution 


calls for the phaseout of HCFCs by 2020 if feasible and no later 


than 2040 in any case.  


E. Advance Notice of Proposed Rulemaking Regarding Recycling 


   On May 1, 1990, EPA published an advance notice of proposed 


rulemaking (ANPRM, 55 FR 18256) addressing issues related to 


the development of a national CFC recycling program. This notice 


emphasized that recycling is important because it would allow 


the continued use of equipment requiring CFCs for service past 


the year in which CFC production is phased out, thereby eliminating



or deferring the cost of early retirement or retrofit of such 


equipment. The Agency continues to believe that the continued 


use of these substances in existing equipment that recycling 


would allow can serve as a useful bridge to alternative products 


while minimizing disruption of the current capital stock of 


equipment.  


   The ANPRM asked for comment on the feasibility of recycling 


in various CFC end uses and also asked for comment on methods, 


such as a deposit/refund system, that could be employed to
encourage 


recycling. The Agency received 110 public comment letters in 


response to the ANPRM. In general, most commenters recognized 


the need for recycling to be established to help efforts to 


protect the ozone layer and to provide a source of refrigerant 


to service existing capital equipment after the phaseout of 


CFC production is complete.  


F. Clean Air Act Amendments of 1990 


   The Clean Air Act Amendments of 1990, signed November 15, 


1990, include requirements for controlling ozone-depleting
substances 


that are generally consistent with, but in some cases more
stringent 


than those contained in the Montreal Protocol as revised in 


1990. For the substances covered by the revised Protocol's control 


measures, title VI of the Act calls for a phaseout of CFCs by 


January 1, 2000 with deeper interim reductions and, in the case 


of methyl chloroform, an earlier phase out date (2002 instead 


of 2005). For the HCFCs, title VI requires use restrictions, 


a production freeze in 2015 and a phaseout in 2050. EPA issued 


a temporary final rule on March 6, 1991 implementing the production



and consumption limits contained in the Act for calendar year 


1991. (See 56 FR 9518.) The Agency published proposed regulations 


for 1992 and beyond on September 30, 1991 (See 56 FR 49548).


   In addition to the phaseout of ozone depleting substances, 


title VI includes a variety of other provisions intended to 


reduce emissions of ozone-depleting substances. Section 608, 


the foundation for the regulations proposed today, provides 


for EPA to promulgate regulations to achieve the "lowest achievable



level" of emissions of ozone-depleting substances and to maximize 


recycling of such substances. Section 608 also bans the knowing 


venting of ozone-depleting substances during the maintenance, 


service, repair, or disposal of appliances and industrial process 


refrigeration. Section 609 establishes a specific program requiring



the recovery and recycling of refrigerant used in motor vehicle 


air conditioners, specifically requires training and certification 


of technicians, and restricts the sale of small containers of 


CFCs. Other title VI sections call for mandatory labelling, 


a ban on nonessential products, and a program to review the 


safety of alternatives to class I and class II substances.


II. Section 608 of the Clean Air Act


   Section 608 of the Clean Air Act, as amended in 1990, provides 


the legal basis for this rulemaking. It requires EPA to establish 


a comprehensive program to limit emissions of ozone depleting 


substances during their use and disposal.


   Section 608 is divided into three subsections. In brief, 


the first requires regulations to reduce the use and emission 


of class I substances (CFCs, halons, carbon tetrachloride, and 


methyl chloroform) and class II substances (HCFCs) to the lowest 



achievable level, and to maximize the recycling of such substances.



The second subsection requires that the regulations promulgated 


pursuant to subsection (a) contain requirements concerning the 


safe disposal of class I and class II substances. Finally, the 


third subsection establishes self-effectuating prohibitions 


on the venting into the environment of class I or class II
substances, 


and eventually their substitutes, during servicing and disposal 


of air conditioning or refrigeration equipment.


   In particular, subsection (a) of section 608 requires EPA 


to promulgate regulations "establishing standards and requirements 


regarding the use and disposal" of both class I substances and 


class II substances. The regulations required are to "reduce 


the use and emission of such substances to the lowest achievable 


level" and are to "maximize the recapture and recycling of such 


substances." Subsection (a) calls for EPA to promulgate such 


regulations with respect to "the use and disposal of class I 


substances during the service, repair, or disposal of appliances 


and industrial process refrigeration" by January 1, 1992.
(Appliance 


is defined by section 601(1) as "any device which contains and 


uses a class I or class II substance as a refrigerant and which 


is used for household or commercial purposes, including any 


air conditioner, refrigerator, chiller, or freezer." EPA believes 


that motor vehicle air conditioners (MVACs) are included within 


the scope of the term "appliance" but that the servicing
regulations 


promulgated pursuant to section 609 of the Act eliminate the 


need to promulgate servicing regulations for MVACs under section 


608. MVACs, however, will be subject to disposal regulations 


proposed today under section 608.) These regulations were to 


become effective by July 1, 1992. Paragraph (2) of subsection 


(a) expands the scope of the recycling and emission reduction 


regulations by requiring EPA to promulgate additional regulations 


by November 15, 1994, that establish standards and requirements 


regarding the use and disposal of both class I and class II 


substance not covered by the initial set of regulations, i.e., 


all other uses of class I and class II substances. These
regulations 


are to go into effect not later than 12 months after their
promulgation. 


Subsection (a) further provides that the regulations promulgated 


pursuant to it may include requirements to use alternative
substances, 


to minimize the use of class I or class II substances, or to 


promote the use of safe alternatives to class I and class II 


substances.


   Subsection (b) of section 608 requires that the regulations 


under section 608(a) establish standards and requirements for 


the safe disposal of class I and class II substances. These 


are to include (1) requirements that such substances contained 


"in bulk in appliances, machines, or other goods" be removed 


prior to the disposal of such items or their delivery for
recycling; 


(2) requirements that "any appliance, machine or other good 


containing a class I or class II substance in bulk" be "equipped 


with a servicing aperture or an equally effective design feature 


which will facilitate the recapture of such substance;" and 


(3) requirements that products in which a class I or class II 


substance is an "inherent element" be disposed of "in a manner 


that reduces, to the maximum extent practicable, the release 


of such substance into the environment."


   The provisions of subsections (a) and (b) ultimately (by 


November, 1994) apply to all uses of class I and class II
substances, 


including air conditioning and refrigeration, solvents, foam 


blowing, and fire control. However, these subsections focus 


first on the use and disposal of refrigerants during the service, 


repair, or disposal of air conditioning or refrigeration equipment.


   Refrigerants also receive special emphasis in subsection 


(c) of section 608, which provides in paragraph (1) that, effective



July 1, 1992, it is "unlawful for any person, in the course 


of maintaining, servicing, repairing, or disposing of an appliance 


or industrial process refrigeration, to knowingly vent or otherwise



knowingly release or dispose of" class I or class II refrigerants 


in a manner that "permits such substances to enter the
environment." 


Certain de minimis releases are exempted from this
self-effectuating 


prohibition. As discussed below in section III. D, EPA is proposing



that, once the requirements of the regulations proposed today 


go into effect, "de minimis releases" be interpreted to mean 


releases that occur when the recycling and recovery requirements 


of this regulation are followed. Section 608(c)(2) extends the 


prohibition on venting to substances that are substitutes for 


class I and class II refrigerants effective November 15, 1995, 


unless the Administrator determines that such venting or releases 


do not pose a threat to the environment. The Agency notes that 


since MVACs are covered by the term "appliance," the servicing 


and disposal of MVACs is subject to the prohibition on venting. 


   Today's notice, proposing refrigerant recycling and safe 


disposal requirements, is a major step in the implementation 


of section 608. EPA research indicates that in all air conditioning



or refrigeration sectors, emissions during servicing and disposal 


of equipment account for between 50 and 94 percent of total 


emissions during the life cycle of the equipment (Regulatory 


Impact Analysis: the National Recycling and Emission Reduction 


Program, (RIA)). The recovery and recycling requirements proposed 


today should sharply reduce emissions during servicing and
disposal, 


bringing total potential emissions from 41,000 metric tons per 


year to approximately 15,000 metric tons per year (RIA). (These 


figures are weighted by ozone depletion potential; unweighted 


figures are higher). In those sectors where leakage during use 


accounts for a significant percentage of total emissions, EPA 


will evaluate the need to establish standards to minimize emissions



during this life cycle stage. Finally, EPA will evaluate the 


need to regulate non-refrigerant applications of class I and 


class II compounds under section 608. These regulations may 


include requirements for emission-reducing engineering controls 


and work practices and/or requirements to use alternative
substances 


in those uses for which substitutes exist. In determining whether 


or not to take further action under section 608, EPA will consider 


the incremental costs and benefits of such action. 


III. Today's Proposed Rule 





A. Equipment Affected 


   Today's proposed rule applies to the servicing and disposal 


of most air conditioning and refrigeration equipment, including 


household air conditioners and refrigerators, commercial air 


conditioners and chillers, commercial refrigeration, industrial 


process refrigeration, refrigerated transport, and air conditioning



in vehicles not covered by EPA's regulations under section 609 


of the Clean Air Act (which apply to the service of motor vehicle 


air conditioners, or MVACs). The proposed rule also applies 


to the disposal of MVACs. Following is a description of the 


major categories of equipment that will be affected by the rule: 


   Household Refrigeration. This category consists of refrigerators



and freezers intended primarily for household use, though they 


may be used outside the home (e.g., in an office). In terms 


of the number of units currently in operation, this is the largest 


sector affected by this rule, with an estimated 159 million 


units. The amount of refrigerant (charge) in each of these units, 


however, is quite small relative to the charge in equipment 


in other sectors, ranging from six ounces to approximately one 


pound of CFC-12. The quantity of refrigerant in this sector 


that is available for recycling at servicing and disposal is 


estimated to be approximately 6,000 metric tons per year. (This 


and other estimates in this section are based on figures from 


1990.) This makes up approximately 17% of the total available 


from the sectors affected by this rule when these quantities 


are weighted by the ozone depletion potentials (or ODPs) of 


the refrigerants. Because servicing is relatively rare in this 


sector, approximately 90% of this 17% would be recovered at 


disposal. 


   Other Refrigerated Appliances. Other refrigerated appliances 


include dehumidifiers, vending machines, ice makers, and water 


coolers. These equipment types have charge sizes and service 


characteristics similar to those in the Household Refrigeration 


sector. The total number of units of these types in current 


operation is approximately 43 million units. The quantity of 


refrigerant in this sector that is estimated to be available 


for recycling at servicing and disposal is 700 metric tons per 


year, which makes up approximately two percent of the total 


available from the sectors affected by this rule.


   Residential Air Conditioning. This sector includes window 


units, packaged terminal air conditioners, central air
conditioners, 


light commercial air conditioners, and heat pumps. There are 


approximately 133 million units in this sector, making it the 


second largest. The residential air conditioning sector is similar 


to the household refrigeration and other appliances sectors 


because the equipment stock is large, the equipment is infrequently



serviced, and charge sizes are small (4-7 pounds). The quantity 


of refrigerant in this sector that is available for recycling 


at servicing and disposal is estimated to be 1600 metric tons 


per year (when weighted by the ozone-depletion potential of 


the refrigerant), which makes up approximately five percent 


of the total available from the sectors affected by this rule. 


This figure is lower than that for household refrigeration because 


residential and light commercial air conditioning relies
exclusively 


upon HCFC-22, which has approximately five percent of the ozone-


depletion potential of CFC-12.


   Transport Refrigeration. The Transport Refrigeration sector 


consists of refrigerated ship holds, truck trailers, railway 


freight cars, and other shipping containers. With only
approximately 


one million transport refrigeration units currently in use, 


this sector is relatively small. Trailers, railway cars, and 


shipping containers are commonly charged with CFC-12. Ship holds, 


on the other hand, rely on HCFC-22 and ammonia. The average 


charge size in this sector is approximately 18 pounds, which 


is relatively small compared to all but household sectors. The 


quantity of refrigerant in this sector that is estimated to 


be available for recycling at servicing and disposal is 1900 


metric tons per year, which makes up approximately five percent 


of the total available from the sectors affected by this rule. 


Unlike equipment in the household sectors, equipment in the 


transport refrigeration sector is usually serviced every year. 


Thus, refrigerant recovered and recycled at servicing would 


account for approximately 25% of the total recovered and recycled 


in this sector.


   Retail Food. The retail food sector includes refrigerated 


equipment found in supermarkets, convenience stores, restaurants, 


and other food service establishments. The equipment includes 


small reach-in refrigerators and freezers, refrigerated display 


cases, walk-in coolers and freezers, as well as large parallel 


systems. Convenience stores and restaurants typically use stand-


alone refrigerators, freezers, and walk-in coolers. In contrast, 


supermarkets usually employ large parallel systems, which connect 


many display cases to a central condensing unit by means of 


extensive refrigerant piping. Because the piping required to 


connect all of the cases may be miles long, these systems can 


contain charges of over 500 pounds. Charges are typically CFC-


12, CFC-502, or HCFC-22. The estimated total stock of retail 


food equipment is approximately 2.5 million units. The quantity 


of refrigerant in this sector that is estimated to be available 


for recycling at servicing and disposal is 9,000 metric tons 


per year, which makes up approximately 26% of the total available 


from the sectors affected by this rule.


   Because of the large charge sizes and frequency of servicing 


in the retail food sector, EPA believes that recycling in the 


sector is already widespread.


   Cold Storage Warehouses. Cold storage warehouses are used 


to store meat, produce, dairy products, and other perishable 


goods. There are approximately 665 million cubic feet of
refrigerated 


space in cold storage warehouses throughout the United States. 


This sector is similar to the retail food sector, but its equipment



is serviced even more frequently (up to four times each year) 


and can be charged even more frequently (up to four times each 


year) and can be charged with even greater quantities of
refrigerant. 


The quantity of refrigerant in this sector that is estimated 


to be available for recycling at servicing and disposal is 80 


metric tons per year, which makes up less than one percent of 


the total available from the sectors affected by this rule. 


As in the retail food sector, EPA believes that recycling is 


already widespread in this sector. 


   Commercial Comfort Air Conditioning. Chillers are used to 


regulate the temperature and humidity in offices, hotels, shopping 


centers, and other large buildings. There are approximately 


167,000 units currently installed, making this sector the smallest 


one affected by the recycling rule in terms of stock size. 


   There are three major types of chillers: Centrifugal,
reciprocating, 


and screw. Each of these is named for the type of compressor 


employed. Centrifugal chillers, used to cool areas ranging from 


30,000 to 600,000 square feet, are generally the largest and 


can be charged with up to 900 kg (about 2000 pounds) of
refrigerant. 


These chillers may use CFC-11, CFC-12, CFC-500, or HCFC-22. 


(Recently, centrigual chillers utilizing HCFC-123 have been 


introduced to the market; however, these new chillers currently 


have a very small fraction of the market and are therefore not 


included in this analysis.) Reciprocating chillers, used to 


cool areas of less than 30,000 feet, are generally the smallest 


and typically contain charges of about 160 pounds of CFC-12 


or HCFC-22. Screw chillers are used to cool areas from 30,000 


to 100,000 square feet and are charged with about 500 pounds 


of HCFC-22. All of the systems are serviced frequently. The 


quantity of refrigerant in this sector that is available for 


recycling at servicing and disposal is estimated to be 5200 


metric tons per year, which makes up approximately 14% of the 


total available from the sectors affected by this rule. 


   Chillers are long-lasting relative to most air conditioning 


and refrigeration equipment. Most will last over 20 years and 


some will last 30 years or more. EPA believes that recovery 


and recycling is already common in the chiller sector due to 


the large charges of refrigerant involved. 


Industrial Process Refrigeration 


   The industrial process refrigeration sector includes industrial 


ice machines and ice rinks, as well as many complex, customized 


systems used in the chemical, pharmaceutical, petrochemical, 


and manufacturing industries. Equipment in this sector is often 


critical to the continuous production of valuable materials. 


As a result, industrial process equipment is usually designed, 


manufactured, and installed with special care to minimize down-


time for servicing and repair. 


   This sector uses a variety of refigerants, including CFC-


11, CFC-12, CFC-500, CFC-502, and HCFC-22. Charge sizes can 


be very large, ranging from 750-3000 lbs for ice rinks, and 


rising as high as 20,000 lbs for built-up centrifugal units. 


The quantity of refrigerant in this sector that is available 


for recycling at servicing and disposal is estimated to be 2000 


metric tons per year, which makes up approximately six percent 


of the total available from the sectors affected by this rule. 


Due to the high reliability of industrial process equipment, 


servicing is uncommon, and most recovery will occur at disposal. 


EPA believes that recycling is already common in this sector. 


Motor Vehicle Air Conditioners (MVACs) 


   Motor vehicle air conditioners (MVACs) include air conditioners 


in automobiles and trucks. These recycling regulations only 


affect the disposal of MVACs, because the servicing of MVACs 


is covered by regulations implementing section 609 of the Clean 


Air Act Amendments. Nevertheless, with approximately 119 million 


MVACs currently on the road, this sector is one of the largest 


sectors affected by the recycling rule. Most MVACs used CFC-


12, but some now use HFC-134a. 


   MVACs have the highest leakage rates of refrigerant charges 


of any equipment type affected by the Recycling Rule. Only 40 


percent of all MVACs still contain a refrigerant charge at
disposal. 


The original charge, moreover, is small (two to four pounds). 


However, the quantity of refrigerant in this sector that is 


available for recycling at disposal is estimated to be 9000 


metric tons per year, which makes up approximately 25% of the 


total available from the sectors affected by this rule. 


Comfort Cooling in Vehicles Other Than Trucks and Automobiles 


   Although the servicing of MVACs is covered by regulations 


implementing section 609 of the Act, the servicing (and disposal) 


of air conditioners in other vehicles, such as trains, airplanes, 


ships, buses, construction equipment, and farm vehicles would 


be covered by these recycling regulations. Due to the lack of 


data available on the cooling systems used in these applications, 


these uses were not analyzed. However, the quantity of refrigerant 


available for recycling from this sector is expected to comprise 


only a small fraction of the total available from the sectors 


affected by this rule.


B. Factors Considered in the Development of this Proposal


   Section 608 of the Clean Air Act provides the statutory basis 


for the standards and requirements contained in these proposed 


regulations. The statutory standards against which the regulations 


concerning the use and disposal of ozone-depleting substances 


are to be measured is whether they "reduce the use and emission 


of such substances to the lowest achievable level" and "maximize 


the recapture and recycling of such substances." EPA believes 


that, in the context of recycling, these standards are
complementary, 


i.e., that maximizing recycling will also mean reducing the 


use and emission of these substances to the lowest achievable 


level. EPA also believes that these standards bear a relationship 


to the de minimis releases permitted notwithstanding the general 


prohibition on venting or other releases contained in section 


608(c). In other words, emissions that occur while complying 


with EPA's recovery and recycling requirements, which achieve 


the lowest achievable level of emissions, will only be de minimis 


releases.


   In applying the statutory standards concerning use, emissions, 


and recycling, EPA is taking into account both technological 


and economic factors. The phrases "lowest achievable level" 


and "maximize recycling" are not defined in the Act. EPA does 


not believe that these standards are solely technological in 


nature, but rather contemplate a role for economic factors in 


determining the lowest "achievable" level of emissions and maximum 


amount of recycling. EPA notes that section 608(a)(3) specifically 


refers to the use of safe alternatives pursuant to section 612, 


which sets out the policy that "to the maximum extent practicable, 


class I and class II substances shall be replaced" by other 


chemicals, products, or manufacturing processes. Terminology 


such as "maximum extent practicable" allows for the consideration 


of economic factors. EPA also notes that in other provisions 


of the Clean Air Act, similar terms have been used that contemplate



the incorporation of cost and economic factors. See, e.g., section 


202(a)(3)(A)(i) (providing for emissions standards for heavy-


duty vehicles that "reflect the greatest degree of emission 


reduction achievable through the application of technology which 


the Administrator determines will be available * * * giving 


appropriate consideration to cost, energy, and safety factors"); 


section 213(a)(3) (using similar language in the context of 


emission standards for non-road engines). Thus, in EPA's view, 


there is nothing inherent in the use of the terms "achievable" 


or "maximize" that precludes the consideration of economic factors.


   Furthermore, this view is consistent with the legislative 


history of section 608. In a statement made on the floor of 


the House of Representatives shortly before passage of the Clean 


Air Act Amendments of 1990, Representative Ralph Hall stated 


that: "In promulgating regulations [under section 608] the
Administrator 


shall take into account the extent to which emissions reductions 


can be achieved, the costs and benefits of implementing available 


controls, and the time before which certain uses may no longer 


rely on the covered substances." (Cong. Rec. H 12907 (Oct. 26, 


1990).) See also statement of Rep. Walgren (Cong. Rec. 12937 


(Oct. 26, 1990).)


   The stringency of the regulations promulgated to implement 


these standards will also be affected by the amount of leadtime 


between their date of promulgation and their effective date. 


The longer the leadtime, the more time there will be for
technological 


innovations and development to occur, thereby permitting the 


establishment of more stringent standards. Conversely, shorter 


leadtimes necessitate standards based more on the degree of 


emission control and performance achievable by equipment already 


available or equipment that will be available in the near future. 


With respect to the present set of regulations, the leadtime 


is necessarily short as section 608(a)(1) provides for an effective



date of July 1, 1992, for the regulations covering the use and 


disposal of class I substances used in appliances and industrial 


process refrigeration. (This date also coincides with the effective



date of the venting prohibition contained in section 608(c) 


for releases of class I and class II refrigerants from appliances 


and industrial process refrigeration.) Moreover, for regulations 


authorized by section 608(a)(2), the initial effective date 


must be within 12 months of promulgation.


   EPA has considered these factors in developing these
regulations, 


and the Agency believes that it has designed a program that 


will achieve the lowest achievable level of emissions and maximize 


recycling, taking into account in an appropriate manner the 


technology available, costs, benefits, and the leadtimes involved. 


Through extensive discussions with industry representatives 


and environmental organizations, EPA has attempted to identify 


significant emissions and methods for controlling them during 


the repair, service, and disposal of air conditioning or
refrigeration 


equipment. In many cases, the proposed requirements would mandate 


activity already being undertaken by standard-setting and equipment



certification organizations in the heating, ventilation, air 


conditioning, and refrigeration (HVAC/R) sector. They are also 


very similar to the steps being taken to recycle refrigerant 


in MVACs, an area where recycling has been successfully
implemented.


   EPA has attempted to develop a regulatory program that
accommodates 


the wide variety of sizes and types of equipment subject to 


this regulation. In setting its efficiency standards for recycling 


and recovery equipment, EPA has considered among other factors 


both the charge size and frequency of servicing for different 


types of equipment. In general, as charge size and frequency 


of servicing increase, potential emissions increase, and higher 


recovery efficiencies are justified. For instance, the household 


refrigeration and other refrigerated appliances categories that 


combine to make up the "small appliances" category in today's 


proposed rule have tiny charges and are serviced infrequently. 


Under today's proposed rule, recovery equipment in this category 


would be subject to a standard that requires recovery of between 


80 and 90% of the refrigerant (depending upon whether or not 


the compressor of the small appliance is operational). On the 


other hand, equipment containing more than 50 lbs of charge 


would be subject to a standard that requires recovery of over 


99% of the refrigerant. Equipment standards are discussed in 


detail in section III.F.


   EPA has also considered typical methods of disposal in
developing 


these regulations. Under this proposal, equipment that is typically



dismantled on-site before disposal (retail food refrigeration, 


cold storage warehouse refrigeration, chillers, and industrial 


process refrigeration) must have the refrigerant removed and 


recovered in accordance with EPA's proposed requirements for 


servicing. For these types of equipment, the persons who perform 


servicing usually also perform disposal. This is generally not 


the case, however, for smaller items such as household
refrigerators 


and freezers, room air conditioners, and motor vehicle air
conditioners. 


This equipment is disposed of by consumers and generally enters 


the waste stream with the charge intact. EPA is proposing special 


safe disposal requirements for this equipment, which would make 


the final person in the disposal chain (e.g., a scrap metal 


recycler) responsible for ensuring that refrigerant has been 


recovered from equipment before the final disposal of the
equipment. 


Equipment covered by these requirements also includes
dehumidifiers, 


water coolers, and other relatively portable equipment in addition 


to household refrigerators and freezers and MVACs. EPA's safe 


disposal program is discussed in detail in section III.L.


   Although EPA is not expressly required to include class II 


substances in the recycling regulations to become effective 


on July 1, 1992, EPA is proposing to include class II substances 


in today's proposed rule for a number of reasons. First, the 


prohibition on venting that became effective on July 1 covers 


both class I and class II substances, and EPA considers it
desirable 


to provide a clear, consistent framework for fully implementing 


the prohibition on venting for all refrigerants. The agency 


believes that this framework will minimize confusion and maximize 


compliance with the prohibition. Second, the goals of this
regulation, 


to minimize refrigerant emissions and to help ensure that a 


supply of high-quality refrigerant is available to service
equipment 


in the future, apply to both class I and class II refrigerants. 


Without specific requirements, recycling may proceed improperly, 


leading to excessive HCFC emissions, contamination of refrigerant, 


and damage to equipment. Third, most technicians routinely work 


with both types of refrigerants and therefore would need the 


equipment to handle refrigerants in accordance with the rule 


even if class II substances were not included. Industry
representatives 


on the STOPAC Subcommittee for Recycling agreed with this rationale



and with the inclusion of class II substances in the regulation. 


While EPA's Regulatory Impact Analysis (RIA) does not now
explicitly 


calculate the incremental net benefits of addressing class II 


substances in this regulation (as opposed to in a regulation 


to be promulgated by November, 1994), the final RIA will address 


this issue. EPA requests comment on the costs and benefits of 


including class II substances in the regulation.


C. Overview of Proposed Requirements


   EPA's proposal has three main elements, which, taken together, 


satisfy the criteria of section 608 concerning recycling, emissions



reduction, and disposal. First, the Agency would require
technicians 


servicing and disposing of air conditioning and refrigeration 


equipment to observe certain service practices that reduce
refrigerant 


emissions. Second, EPA would establish equipment and reclaimer 


certification programs. These would have the goals of verifying 


(1) that all recycling or recovery equipment sold was capable 


of minimizing emissions and (2) that reclaimed refrigerant on 


the market was of known and acceptable quality to avoid equipment 


failures from contaminated refrigerant. Third, to implement 


the safe disposal requirements of section 608, EPA would require 


that ozone depleting refrigerants in appliances, machines, and 


other goods be removed from those items prior to their disposal, 


and that all air conditioning and refrigeration equipment except 


for small appliances and room air conditioners be provided with 


a servicing aperture that would facilitate recovery of the
refrigerant. 


In addition to the three main elements of its proposal, EPA 


is requesting comment on the need for EPA involvement in technician



education.


   In order to allow the regulated community sufficient time 


to come into compliance with the certification requirements, 


EPA proposes to phase them in over a period of twelve months. 


In addition, the Agency proposes to "grandfather in" equipment 


meeting certain minimum requirements set forth in Section III. 


These grandfathering provisions are intended to encourage the 


regulated community to begin recycling as soon as possible using 


available equipment rather than delaying action until certified 


equipment is available.


   Section 608(a) of the Act specifies an initial effective 


date for these regulations of July 1, 1992. EPA recognizes that, 


due to the fact that these regulations have not been proposed 


until today, a July 1, 1992 effective date is not possible for 


most portions of them. For certain portions of them, however, 


a July 1, 1992, effective date would still be possible, albeit 


retroactively. EPA believes that a July 1, 1992 effective date 


is appropriate for the provision of the proposed regulations 


prohibiting the venting of refrigerants because the prohibition 


on venting contained in section 608(c) of the Act is
self-effectuating 


and went into effect on July 1, 1992, notwithstanding the lack 


of final regulations under section 608. For other portions of 


the regulations, EPA is proposing various effective dates in 


order to allow sufficient lead time for the affected industry 


to comply. EPA requests comment on what the appropriate effective 


dates would be for the different provisions of the regulations, 


taking into account the amount of leadtime necessary to comply 


with these new regulatory requirements and the proposed
grandfathering 


provisions. EPA also requests comment on the feasibility and 


implications of adopting a retroactive effective date in the 


final regulations.


D. Public Participation 


   EPA has worked extensively with outside groups in developing 


this proposal. In particular, the Agency has established and 


has met repeatedly with the Subcommittee for Recycling and
Emissions 


Reduction of EPA's Stratospheric Ozone Protection Advisory
Committee 


(STOPAC). The STOPAC is a Federal Advisory Committee chartered 


in 1989 under the Federal Advisory Committee Act, 5 U.S.C. App. 


section 9(c), to provide independent counsel to EPA on specific 


issues affecting the international negotiations and domestic 


implementation of the Montreal Protocol. Since the enactment 


of the Clean Air Act Amendments in 1990, the STOPAC has also 


provided advice on the implementation of Title VI of this
legislation. 


The Subcommittee for Recycling has over 50 members representing 


air conditioning and refrigeration equipment manufacturers, 


wholesalers, services, and users, manufacturers of recycling 


and recovery equipment, refrigerant manufacturers and reclaimers, 


educational organizations, state and local governments, and 


environmentalists. To date, EPA has met with members of the 


Subcommittee six times: The Subcommittee as a whole has met 


twice, and smaller groups have met to discuss equipment
certification, 


technician certification, reclaimer certification and safe
disposal. 


Summaries of these meetings are available in the public docket 


for this rulemaking. 


   EPA has also worked with the air conditioning and refrigeration 


industry's primary standards-setting organizations, the Air 


Conditioning and Refrigeration Institute (ARI) and the American 


Society of Heating, Refrigeration and Air-Conditioning Engineers, 


Inc. (ASHRAE), in developing its proposal. Wherever appropriate, 


EPA has incorporated standards and guidelines from these
organizations 


into the proposed rule. Examples of incorporated standards include 


the ARI Standard 700-1988, Specifications for Fluorocarbon
Refrigerants, 


(Appendix A to the proposed regulations), and the ARI Standard 


740-1991, Performance of Refrigerant Recovery, Recycling, and/or 


Reclaim Equipment, (Appendix B to the proposed regulations). 


EPA has also considered the ASHRAE Guideline 3, Reducing Emission 


of Fully Halogenated Chlorofluorocarbon (CFC) Refrigerants in 


Refrigeration and Air-Conditioning Equipment and Applications, 


in developing its proposed rule. 


   In addition to convening the Subcommittee for Recycling, 


EPA has met with various industry representatives to gather 


data on refrigerant emissions, to better understand current 


industry practices, and to discuss a range of technical issues. 


The data on refrigerant emissions were used to update EPA's 


vintaging analysis, which analyzes emissions by equipment type 


and life cycle stage (e.g., manufacturing, use, servicing, or 


disposal). This analysis has been used to calculate the potential 


costs and benefits of this rule and to identify opportunities 


for further emissions reductions. The data used in the analysis 


is presented in the Regulatory Impact Analysis (RIA) for this 


proposal, also available in the public docket. Industry groups 


that have provided or commented on data include appliance
manufacturers, 


chiller manufacturers and services, industrial process
refrigeration 


manufacturers and users, commercial refrigeration manufacturers 


and users, refrigerated transport manufacturers, servicers and 


users, and manufacturers and users of comfort air cooling systems 


for commercial vehicles. 


E. Definitions and Interpretations 





Active Recovery Device 


   Recovery devices used with refrigerators and freezers and 


other small appliances can be divided into two main types: Active 


and passive. While active equipment has its own compressor to 


pump refrigerant out of the refrigerator system, passive equipment 


relies solely upon the compressor in the small appliance and/or 


the pressure of the refrigerant in the appliance to recover 


the refrigerant. EPA proposes to define these two types of
equipment 


accordingly. The distinction is important because active and 


passive recovery devices differ in their recovery efficiencies 


and other performance characteristics, and EPA is proposing 


different certification standards for them. 


Appliance 


   The Act defines "appliance" as "any device which contains 


and uses a class I or class II substance as a refrigerant and 


which is used for household or commercial purposes, including 


any air conditioner, refrigerator, chiller, or freezer." In 


today's proposed rule, EPA is proposing that this language also 


be used in the regulatory definition of appliance. 


   EPA interprets the Act's definition of appliance to include 


all the sectors of air conditioning and refrigeration equipment 


described under section III.A. above, including household
refrigerators 


and freezers (which may be used outside the home), other
refrigerated 


appliances, residential and light commercial air conditioning, 


transport refrigeration, retail food refrigeration, cold storage 


warehouses, commercial comfort air conditioning, motor vehicle 


air conditioners, comfort cooling in vehicles not covered under 


section 609, and industrial process refrigeration. (In sections 


608(a) and 608(c) the Act refers specifically to "industrial 


process refrigeration," a term that is not defined. EPA believes 


that all refrigeration equipment categorized as industrial process 


refrigeration in section III.A. above also falls within the 


broad statutory definition of "appliance.")  


   The Act's definition of "appliance" has one minor limitation: 


The reference to the use of devices for "household or commercial 


purposes." While these purposes encompass virtually all uses 


of devices containing and using refrigerants, EPA does not believe 


that they encompass devices containing and using refrigerants 


that are designed for and used solely in a military application. 


Thus, the Act's definition of appliance does not appear to include,



for example, a refrigeration unit designed only for and used 


only in a nuclear submarine. If, however, the refrigeration 


equipment used in a military application is identical to equipment 


used in a commercial application, then it is covered by the 


Act's definition. For example, a room air conditioner used on 


a military base is still considered an appliance even through 


the use of that particular piece of equipment may not be for 


commercial or household purposes. Similarly, although a
refrigerator 


in some other government facility is not used for household 


or commercial purposes, that refrigerator is still considered 


an appliance because that identical kind of equipment is used 


for household or commercial purposes in other contexts.  


   This interpretation is consistent with section 118 of the 


Act, which provides that "[e]ach department, agency,
instrumentality 


of executive, legislative, and judicial branches of the Federal 


Government * * * shall be subject to, and comply with, all Federal,



State, interstate, and local requirements, administrative
authority, 


and process and sanctions respecting the control and abatement 


of air pollution in the same manner, and to the same extent 


as any non governmental entity." Section 618 of the Act explicitly 


provides that the requirements of Title VI concerning the
protection 


of the stratospheric ozone layer "shall be treated as requirements 


for the control and abatement of air pollution within the meaning 


of section 118."  


   Although EPA believes that equipment designed and used
exclusively 


for military purposes falls outside the definition of "appliance," 


EPA believes that it has the authority under section 608(a)(2) 


to regulate the use and emissions of refrigerant from such
equipment. 


EPA requests comment on whether it should pursue such regulation. 


Approved Equipment Testing Organization  


   EPA proposes to define Approved Equipment Testing Organization 


as any organization which has applied for and received approval 


from EPA to test recycling and recovery equipment.  


Certified Refrigerant Recycling Equipment  


   EPA proposes to define Certified Refrigerant Recycling Equipment



as equipment certified by an approved testing organization to 


meet EPA's final standards or equipment purchased before [6 


months after publication of the final rule] that meets EPA's 


standards for grandfathered equipment.  


High-pressure Appliance  


   Because the physical properties of high, very high,
intermediate, 


and low pressure refrigerants differ, EPA proposes to establish 


somewhat different requirements for technicians and equipment 


servicing high, very high, intermediate, and low pressure
appliances. 


EPA proposes to define high-pressure appliances as appliances 


that uses a refrigerant with a boiling point between -50 and 


0 degrees Centigrade at atmospheric pressure (29.9 inches Hg). 


This definition would include equipment using CFCs 12, 500, 


and 502, and HCFC 22.  


Intermediate-pressure Appliance


   EPA proposes to define intermediate-pressure appliances as 


appliances that use a refrigerant with a boiling point between 


0 and 10 degrees Centigrade at atmospheric pressure (29.9 inches 


Hg). This definition would include appliances using CFC-114 


and possibly blends of CFC-114 and other refrigerants.


Low Loss Fitting


   EPA is proposing to require that recovery or recycling machines 


manufactured after [6 months after publication of the final 


rule], possess low loss fittings or positive shutoff devices. 


EPA proposes to define low loss fitting as any device that is 


intended to establish a connection between hoses, air conditioning 


and refrigeration equipment, or recovery or recycling machines 


and that is designed to close automatically when disconnected, 


minimizing the release of refrigerant from hoses, air conditioning 


or refrigeration equipment, and recovery or recycling machines.


Low-pressure Appliance


   EPA proposes to define low-pressure appliances as appliances 


that use a refrigerant with a boiling point above 10 degrees 


Centigrade at atmospheric pressure (29.9 inches Hg). This
definition 


would include appliances using CFCs 11 and 113, and HCFC 123.


Passive Recovery Device


   As discussed above in the explanation of the term "active 


recovery device," EPA proposes to define a passive recovery 


device as a device that relies solely upon the compressor in 


a small appliance and/or upon the pressure of the refrigerant 


inside a small appliance to remove the refrigerant into an external



container.


Person


   EPA is proposing to require that refrigerant transferred 


between air conditioning or refrigeration equipment owned by 


different persons must be fully reclaimed. EPA proposes to define 


person as any individual or legal entity, including an individual, 


corporation, partnership, association, state, municipality, 


political subdivision of a state, Indian tribe, and any agency, 


department, or instrumentality of the United States, and any 


officer, agent, or employee thereof. This is identical to the 


definition used in the regulations concerning the production 


and consumption of ozone-depleting substances (40 CFR 82.3(r)).


Process Stub


   EPA is proposing to require that small appliances and room 


air conditioners sold after July 1, 1993, be provided with a 


process stub to facilitate removal of the refrigerant at servicing.



The Agency is proposing to define process stub as a length of 


tubing that provides access to the refrigerant inside a small 


appliance or room air conditioner and that can be resealed at 


the conclusion of repair or service.


Reclaim


   EPA is proposing to adopt a slightly modified form of ASHRAE's 


definition of "reclaim." According to ASHRAE, to reclaim
refrigerant 


is to:


   Reprocess refrigerant to new product specifications by means 


which may include distillation. Will require chemical analysis 


of the refrigerant to determine that appropriate product
specifications 


are met. This term usually implies the use of processes or
procedures 


available only at a reprocessing or manufacturing facility.


EPA is refining this definition to refer specifically to the 


ARI Standard 700-1988, Specifications for Fluorocarbon Refrigerants



(included as Appendix A to the proposed rule) for the "New product 


specifications" and also for the appropriate type of chemical 


analysis to ensure that these specifications are met. For the 


Agency's purposes, the most important part of the definition 


of reclaim is the requirement to chemically analyze the final 


product to verify purity. Without such analysis and verification, 


the Agency will not consider refrigerant to have been reclaimed.


Recover


   EPA also proposes to adopt ASHRAE's definition of "recover:" 


to remove refrigerant in any condition from a system without 


necessarily testing or processing it in any way.


Recycle


   Although the Act's usage of the term "recycle" is very broad, 


encompassing, for instance, the term "reclaim" as defined above, 


EPA proposes to define the term more narrowly in its regulations. 


Once again, EPA is proposing to adopt ASHRAE's definition, with 


minor changes. ASHRAE states that to recycle is to:


   Clean refrigerant for reuse by oil separation and single 


or multiple passes through devices, such as replaceable core 


filter-driers, which reduce moisture, acidity and particulate 


matter. This term usually applies to procedures implemented 


at the field job site or at a local service shop.


The key difference between "recycle" and "reclaim" is that the 


former does not involve chemical analysis of the product. Recycling



essentially encompasses all types of treatment of refrigerant 


that do not involve such chemical analysis. As explained in 


a later section of this notice, EPA is proposing to require 


that all refrigerant changing hands must be fully reclaimed, 


implying that the vast majority of recycling will take place 


on site as opposed to at a local service shop.


Small Appliance


   EPA is proposing to define as "small appliance" air conditioning



or refrigeration equipment containing less than one pound of 


charge during normal operation. Equipment containing less than 


one pound of charge includes household refrigerators, household 


freezers, dehumidifiers, vending machines, and water coolers. 


EPA is also proposing special servicing and safe disposal
requirements 


for these items. EPA requests comment on using the one-pound 


quantity to define them.


Technician  


   EPA is proposing a number of requirements that apply to
technicians. 


EPA proposes to define technician as any person who performs 


maintenance, service, or repair to air conditioning or
refrigeration 


equipment that could reasonably be expected to release CFCs 


or HCFCs into the atmosphere, e.g., installers, contractor
employees, 


in-house service personnel, and in some cases, owners. Technician 


also means any person disposing of air conditioning or
refrigeration 


equipment except for small appliances.  


Very High Pressure Equipment  


   EPA proposes to define very high pressure equipment as air 


conditioning and refrigeration equipment that uses a refrigerant 


with a boiling point below 50 degrees Centigrade at atmospheric 


pressure. This definition would include equipment using
refrigerants 


13 and 503.  


F. Required Practices  


   EPA is proposing to require persons servicing or disposing 


of air conditioning and refrigeration equipment to observe certain 


service practices that minimize emissions of ozone depleting 


refrigerants. The most fundamental of these practices is the 


requirement to recover refrigerant rather than vent it to the 


atmosphere. As noted above, the knowing venting of class I or 


class II refrigerant during servicing or disposal (except for 


de minimis releases that accompany a good faith effort to recycle) 


is expressly prohibited by section 608(c) of the Act after July 


1, 1992.  


   EPA proposes to define venting as any release to the environment



of a class I or class II substance that takes place with the 


knowledge of the technician during the maintenance, servicing, 


repairing, or disposal of air conditioning or refrigeration 


equipment. De minimis releases, as discussed below, are not 


considered venting.  


   As noted above, section 608(c)(1) of the CAA prohibits the 


knowing venting of class I and class II substances from appliances 


or industrial process refrigeration during servicing and disposal. 


However, that section exempts "de minimis" releases associated 


with good faith attempts to recapture and recycle or safely 


dispose of these substances from the prohibition. In their
statement 


prior to the passage of the Clean Air Act Amendments of 1990, 


the Senate managers explained that, "The exception is included 


to account for the fact that in the course of properly using 


recapture and recycling equipment, it may not be possible to 


prevent some small amount of leakage." (Congressional Record 


S16948 (October 26, 1990)). From this statement and the statutory 


text, EPA considers it appropriate to conclude that emissions 


accompanying the proper use of recapture and recycling equipment 


would generally be considered "de minimis." EPA therefore proposes 


to define as "de minimis" those emissions that take place at 


servicing and disposal when: 


   (i) The required practices set forth in 82.158 of this proposed 


regulation are observed and when recovery or recycling machines 


that meet the requirements set forth in 82.158 of this proposed 


regulation are used, or


   (ii) The requirements of the MVAC regulation (40 CFR part 


82 subpart B) are observed.


   Such emissions represent the lowest achievable level of
emissions, 


but because the requirements for recovery and recycling machines 


would vary somewhat from sector to sector and because the charge 


sizes involved vary considerably from sector to sector, the 


quantities considered de minimis would also vary from sector 


to sector.


   1. Evacuation of air conditioning and refrigeration equipment. 


EPA proposes that before air conditioning and refrigeration 


equipment is opened for maintenance, service, or repair, the 


refrigerant in either the entire system or the part to be serviced 


(if the latter can be isolated) must be transferred to a system 


receiver (a component of the system that is designed to hold 


excess refrigerant charge and that can be used to hold the charge 


during servicing or repair) or to a certified recycling or recovery



machine. The same requirements would apply to equipment that 


is to be disposed of, except for small appliances, room air 


conditioners, and MVACs, whose disposal is covered by Section 


III.L below. In order to ensure that the maximum amount of
refrigerant 


possible is captured rather than released, EPA is proposing 


to require that air conditioning and refrigeration equipment 


be evacuated to or below specified levels of vacuum. The Agency 


has considered a number of factors in developing these levels, 


including the technical capabilities, ease of use, and costs 


of recycling and recovery equipment, the possible impact of 


evacuation on the air conditioning and refrigeration equipment, 


the servicing times that would be unnecessary to achieve different 


vacuums, and the amounts of refrigerant that would be released 


under different evacuation requirements and their predicted 


impact on the ozone layer (and indirectly, on human health and 


the environment). Characteristics of recycling and recovery 


equipment are discussed in more detail in section III.G; servicing 


times and the possible impact of evacuation on air conditioning 


and refrigeration equipment are discussed in section a. below.


   The required level of evacuation would vary depending upon 


the type of equipment to be serviced or disposed of and the 


date of manufacture of the recovery or recycling machine (i.e., 


whether it met certification requirements for new equipment 


or had been grandfathered). For small appliances, the requirements 


would also vary depending on the capacities of the recovery 


system used under the circumstances (e.g., with an operating 


vs. a nonoperating refrigerator compressor).


   a. Evacuation requirements for air conditioning and
refrigeration 


equipment besides small appliances. When recovery and recycling 


machines manufactured or imported after [6 months after publication



of the final rule], are employed for recovery, EPA is proposing 


to require evacuation to 0 inches of vacuum, 10 inches of vacuum, 


20 inches of vacuum, 25 inches of vacuum, or 29 inches of vacuum, 


depending on the size and type of air conditioning or refrigeration



equipment being serviced. If grandfathered recovery or recycling 


devices are used, EPA proposes to require evacuation to 0 inches 


of vacuum in very high pressure systems, 4 inches of vacuum 


in high pressure systems, and 25 inches of vacuum in low pressure 


systems and in systems utilizing CFC 114, because the grandfathered



equipment may not be capable of achieving higher levels (see 


Section III.G.). The table below lists requirements for evacuation 


(pressure readings) for each type of air conditioning and
refrigeration 


equipment and for certified and grandfathered recovery and
recycling 


machines.





        Table 1.-Required Levels of Evacuation for Air Conditioning
or        


              Refrigeration Equipment Except for Small Appliances  
          


                                                                   
          


__________________________________________Â___________________________________


                                          ³         Inches of
Vacuum          


                                          ³                   
               


                                         
Ã________________Â__________________


                                          ³ Using recovery
³ Using recovery   


                                          ³  or recycling 
³  or recycling    


Type of air conditioning or refrigeration ³    equipment  
³    equipment     


                equipment                 ³  manufactured 
³  manufactured    


                                          ³ before [6 mos.
³ on or after [6   


                                          ³      after    
³   mos. after     


                                          ³ publication of
³ publication of   


                                          ³   final rule] 
³   final rule]    


______________ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ


                                          ³               
³                  


High pressure equipment with a charge of  ³              4
³             10   


 less than 50 pounds.                     ³               
³                  


High pressure equipment with a charge of  ³              4
³             20   


 more than 50 pounds.                     ³               
³                  


Very high pressure equipment ............ ³              0
³              0   


Intermediate pressure equipment ......... ³             25
³             25   


Low pressure equipment .................. ³             25
³             25   


                                          ³               
³         mm Hg*   


ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ


  *Pressures below 25 inches of vacuum are typically measured in
millimeters  


  (mm) or microns (æ) of mercury absolute rather than in
inches of mercury    


  vacuum. At standard sea-level atmospheric pressure (29.9 inches
of mercury  


  absolute), 25 mm of mercury absolute is approximately equal to
one inch of  


  mercury absolute or 29 inches of mercury vacuum. EPA proposes to
use the    


  absolute rather than relative measure here not only because this
is the     


  standard industry practice but because 29 inches of vacuum cannot
          


  physically be attained in areas where atmospheric pressure
typically falls  


  very near or below 29 inches of mercury absolute (e.g., areas at
high       


  elevation, such as Denver, Colorado).                            
          





   i. Impact of vacuums on high-pressure air conditioning or 


refrigeration equipment. Some industry representatives on the 


STOPAC Subcommittee expressed concern that drawing vacuums on 


high-pressure equipment could have two adverse effects: (1) 


If air conditioning or refrigeration equipment is leaky, drawing 


a vacuum on the equipment may pull air and moisture into the 


equipment and from there into the recycling or recovery device, 


contaminating refrigerant and in some instances, limiting the 


depth of vacuum that can be achieved; and (2) when air conditioning



and refrigeration equipment is opened for service after a vacuum 


has been drawn, air and moisture are drawn into the system in 


greater amounts than they are if the interior of the system 


is at atmospheric pressure. If these contaminants are not removed 


from the system, they can corrode equipment and cause it to 


fail.


   As discussed below in section III.F.1.d., the Agency has 


attempted to provide for situations involving leaky equipment. 


Influxes of air and moisture caused by opening a system whose 


interior pressure is lower than atmospheric pressure may be 


addressed in two ways, according to industry sources. First, 


such influxes may be prevented by breaking the vacuum with dry 


nitrogen. This method, however, requires technicians to carry 


heavy nitrogen cylinders, a procedure that may be impractical 


for servicing equipment located on rooftops or other difficult 


to reach areas. Second, air and moisture may be removed from 


a system by drawing a second, deeper vacuum on the system after 


it is repaired. However, although drawing a second vacuum is 


standard industry practice, the time involved in drawing a deep 


vacuum discourages many technicians from achieving a vacuum 


deep enough to remove all the air and moisture that may have 


entered the system. Thus, a number of service companies recommend 


that their technicians evacuate high pressure systems only to 


atmospheric pressure, minimizing the intrusion of air and moisture.


   EPA requests comment on the option of requiring technicians 


who service small high pressure systems, particularly those 


utilizing HCFC-22, to evacuate these systems only to atmospheric 


pressure. As is discussed further in section III.G. below, the 


Agency is generally willing to consider less stringent standards 


for equipment utilizing HCFC-22 because HCFC-22 has approximately 


five percent of the ozone depletion potential of CFCs 11 and 


12. However, EPA believes strongly that larger systems and systems 


utilizing high-pressure refrigerants besides HCFC-22 should 


be evacuated to levels below atmospheric pressure. Large systems 


utilizing CFC-12 in particular may still contain several pounds 


of refrigerant at atmospheric pressure; for instance, a bank 


of compressors in a grocery store with a charge of 500 pounds 


of CFC-12 (a common quantity) will contain over 10 pounds of 


refrigerant at atmospheric pressure. For these and similar systems,



EPA believes the quantity of refrigerant recovered by pulling 


a deeper vacuum justifies the extra labor required either to 


break the vacuum with nitrogen or to pull a second vacuum deep 


enough to remove all the air and moisture that may enter a system 


below atmospheric pressure. The Agency requests comment on this 


rationale and on the levels of vacuum proposed above.


   ii. Servicing Times. EPA has also considered the amount of 


time technicians would have to spend on the job in order to 


achieve certain vacuums. Each additional unit of vacuum takes 


longer than the preceding one to achieve. Hence, a recovery 


or recycling machine that can achieve a 10 inch vacuum in a 


system in 15 minutes may require another 15 minutes to reach 


12 inches, then another 15 minutes to reach 13 inches, etc. 


However, EPA discussions with industry indicate that in general, 


the vacuums specified above can either be achieved within a 


reasonable time period while the technician is on the job or 


overnight. (Evacuations of large systems are often performed 


overnight.) EPA requests comment on this finding.


   b. Evacuation requirements for small appliances. For reasons 


discussed further in section EPA's proposed evacuation requirements



for small appliances would depend upon whether an active recovery 


device (with a pump) or a passive recovery device (without a 


pump) were employed for refrigerant recovery.


   Technicians using active recovery devices to recover refrigerant



would be required to reduce system pressure to one atmosphere 


(0 psig) (equivalent to 90% capture of refrigerant at 70 F) 


in the sealed system. Because the recovery efficiency of passive 


recovery device is less dependent on a pressure reading than 


on a specific procedure, technicians using passive systems would 


be required to adhere to the servicing procedure certified for 


that recovery system. Certification of passive recovery devices 


and recovery procedures are discussed in more detail in section 


III.G.


   c. Removal of entrained refrigerant from oil. In some cases, 


significant amounts of oil are left behind in a system after 


refrigerant has been recovered. In these cases, simply drawing 


the vacuums specified in table 1 above may not recover a high 


percentage of the refrigerant, because a large percentage of 


the refrigerant in a system may be entrained in the compressor 


oil. For instance, at 80 degrees F and atmospheric pressure, 


50% of the volume of oil in a low pressure chiller is typically 


made up of refrigerant. EPA has two concerns regarding oil
contaminated 


with refrigerant: (1) The refrigerant may be released once the 


system is opened and the oil is exposed to the air, and (2) 


the eventual combustion of the oil (a common method of disposal) 


may create toxic compounds. The latter concern has led EPA to 


classify oil containing certain concentrations of CFCs or HCFCs 


as an off-specification fuel under its RCRA regulations.
(Classification 


of oil as an off-specification fuel is discussed in more detail 


in section III.E.3.) The Agency has similar concerns regarding 


oil removed from the compressor during an oil change.


   There are a number of methods for recovering refrigerant 


entrained in oil The ASHRAE Guideline 3 mentions two, recommending:


   When removing oil from the compressor, it is recommended 


that the crankcase be pumped down to atmospheric pressure to 


remove dissolved refrigerant prior to exposing the oil to the 


atmosphere. Refrigerant in solution may be further reduced by 


use of crankcase heaters (ASHRAE Guideline 3-1990, p. 7).


The Trane company has determined that through the use of heat 


and vacuum, refrigerant concentrations in centrifugal chiller 


oil can be reduced to one percent or lower.


   Recent discussions with industry representatives indicate 


that these methods can be time-consuming and therefore costly. 


For instance, if a heat pump or air conditioner is not operational,



it can take up to 24 hours for a crankcase heater to warm up 


fully, and the Trane method for removing low-pressure refrigerant 


from oil can take several days. In addition, the equipment
necessary 


for transporting the oil and extracting the refrigerant can 


be cumbersome.


   EPA requests comment on the potential of oil in the various 


industry sectors to emit CFCs and HCFCs during or after servicing, 


and on whether it would be appropriate to require technicians 


to follow procedures to extract refrigerant from oil before 


exposing the oil to the atmosphere or disposing of the oil. 


Are there methods for removing most if not all of the refrigerant 


that can be implemented relatively quickly? When would such 


methods be applied? Should they be required even for operations 


such as oil sampling, which involve withdrawing only a small 


fraction of the oil in a system? Are any of the current methods 


for removing refrigerant from oil powerful enough to reduce 


refrigerant concentrations below the levels that trigger
designation 


as an off-specification fuel (4,000 ppm)? If so, even a somewhat 


complicated refrigerant recovery procedure may be preferable 


to generation of material that is difficult to dispose of.


   EPA could require that refrigerant be extracted from oil 


when ease of recovery, high oil volumes, and/or high refrigerant 


concentrations made the effort worthwhile. One relatively simple 


approach would be to require technicians to hold the system 


at a vacuum for a period of time that would vary depending upon 


the type and size of equipment. As refrigerant evaporated out 


of the oil, the system pressure would rise. The technician would 


then be required to pump the system back down to the specified 


vacuum before opening the system for service. (Adding heat to 


the system could expedite this process.) Such a requirement 


would have the additional benefit of permitting any remaining 


liquid refrigerant in the system to evaporate and be recovered.


   d. Evacuation of leaky equipment. Industry representatives 


on the STOPAC Subcommittee of recycling noted that in some cases, 


large leaks made it impossible to draw a deep vacuum on high-


pressure air conditioning or refrigeration equipment. In such 


cases, EPA proposes to allow high pressure equipment to be
evacuated 


to 0 psig (atmospheric pressure) instead of to the levels above. 


A large leak would be defined as one that lowers the pressure 


of a high pressure system to less than two atmospheres (60 inches 


of mercury absolute). Industry members stated that leaks smaller 


than this would not prevent evaluation to the level specified 


in Table 1 (Memorandum from Deborah Ottinger to the Record, 


"Meeting Between EPA and ASHRAE Representatives," November 19, 


1992). EPA requests comment on this proposal.


   2. Leak Repair. Although EPA will consider developing
comprehensive 


regulations to reduce refrigerant leakage during equipment use 


in the next phase of rulemaking under section 608, the Agency 


requests comment on whether it should include in this rule a 


requirement to repair substantial leaks. Such a provision could 


require technicians servicing equipment that leaks more than 


35% of its charge per year to find and repair the leak within 


some period of time, perhaps 30 days after the leak's discovery. 


While technicians would not be required to inspect for leaks 


outside of their normal servicing procedures, they would be 


required to repair leaks that they become aware of during such 


procedures (e.g., by noting that the charge was low by 35% or 


more). This provision would be an emergency, stop-gap measure 


to ensure that technicians repaired large leaks instead of
repeatedly 


"topping off" systems with new refrigerant. A number of industry 


representatives have stated that the latter practice remains 


common, despite the increasing cost of refrigerant.


   The Agency is suggesting the 35% figure because research 


on emissions from equipment in different sectors shows that 


this is five percentage points above the typical annual leak 


rate in the most leak-prone sectors. Rather than adopt a standard 


based on the annual leak rates in the leakiest sectors, however, 


EPA could establish different criteria for different sectors. 


For example, technicians would be required to repair leaks in 


chillers if they released more than 15% of the charge annually 


(chillers typically leak 10% of their charge per year), but 


they would not have to repair leaks in the retail food sector 


unless they released more than 35% of the total charge annually 


(refrigeration in the retail food sector typically leaks 30% 


of the charge per year). By using the typical leak rate of a 


given sector as a bench mark, the Agency is assuming that it 


represents an industry standard for the amount of leakage from 


normally maintained and operated equipment. Leaks that are
significantly 


higher than this benchmark should be worth repairing according 


to most service technicians in the sector. While this approach 


falls short of establishing a lowest achievable level of emissions 


to the extent that typical industry practice falls short of 


that level, it would reduce leaks until needed additional analysis 


can be performed and regulations establishing lowest achievable 


levels of emissions during operation of equipment are promulgated. 


   3. Disposition of Recovered Refrigerant. EPA proposes to 


allow technicians considerable flexibility in the disposition 


of recovered refrigerant. The one restriction (besides the
prohibition 


on venting) that EPA proposes to impose is that refrigerant 


transferred between equipment owned by different persons must 


be reclaimed. As discussed above in the Definitions Section, 


"reclaimed" means that the refrigerant is cleaned to the ARI 


700-1988 standard of purity (Appendix A) and is chemically analyzed



to verify that it meets this standard. (Technically, the
refrigerant 


need not be reprocessed if chemical analysis shows that it already 


meets the ARI 700 standard of purity; however, this is seldom 


expected to be the case.) EPA proposes to implement this
restriction 


by prohibiting the sale or offering for sale of class I and 


class II refrigerants that do not meet the ARI 700 Standard. 


In this requirement, EPA would codify the industry recommendation 


for refrigerant moved off-site. In fact, the requirement would 


apply the standard of purity set forth in ARI 700 somewhat less 


restrictively than ARI itself, which states that the standard 


is intended for refrigerant transferred between any two pieces 


of equipment, even if they are owned by the same person. Under 


this proposed regulation, refrigerant moved between equipment 


owned by the same person, corporation, or governmental entity 


would not need to be either tested or treated. Thus, for instance, 


grocery store chains could move refrigerant from equipment in 


one store to equipment in another without treating it. 


   EPA proposes to focus on changes in ownership of refrigerant 


because such transfers introduce uncertainties into the marketplace



regarding the purity of the refrigerant. Manufacturers of air 


conditioning and refrigeration equipment on the STOPAC Subcommittee



for Recycling states that unless used refrigerant were chemically 


analyzed, there was a significant risk of contaminated or mixed 


refrigerant entering the market and ultimately damaging equipment 


on a large scale. Refrigerant reclaimers have reported finding 


a wide range of contaminants in used refrigerants delivered 


to them. Many of these contaminants (including other refrigerants) 


are not removed by standard recycling machines. EPA is concerned 


not only with the damage that contaminated refrigerant could 


cause, but with the reduction of consumer confidence in the 


quality of recycled refrigerant that might result. Slackened 


demand could lead to the stockpiling (and ultimately, the venting) 


of unwanted used refrigerant. 


   When refrigerant is moved from one piece of equipment to 


another but ownership does not change, the risks to equipment 


are still present, but a single owner is in the position to 


evaluate those risks and they do not present a problem for a 


market in which other consumers are purchasing the used
refrigerant. 


   EPA is particularly concerned that, in the absence of a
requirement 


to reclaim refrigerant before selling it to a new owner, these 


recycling requirements could encourage the development of
"recycling 


centers" that accepted used refrigerant from a wide variety 


of sources without analyzing it. In such cases, uncertainty 


regarding the origin and purity of the refrigerant would be 


compounded by the participation of an intermediate party. In 


addition, if a recycler unknowingly mixed contaminated refrigerant 


into a larger batch, the potential for harm would be multiplied 


accordingly. Consolidation of batches also increases the likelihood



of mixing different refrigerants. In either of these cases, 


the recycled refrigerant would be rendered unusable, making 


its release (either through damage to equipment or deliberate 


venting) far more likely. EPA requests comment on the likelihood 


that without regulation, recycling centers would arise and lead 


to the release of refrigerants into the environment. 


   EPA recognizes that private parties will continue to face 


strong incentives to ensure adequate refrigerant purity in the 


absence of any federal regulation. Purchasers of refrigerant 


have always had the incentive to ensure refrigerant purity; 


yet with the expected increase in refrigerant recycling, the 


cost of ensuring purity might increase. The risks by contaminated 


refrigerant may consist of damage to private property,
specifically, 


potential harm to equipment caused by moisture-, acid-, or oil-


contaminated refrigerant, decreases in equipment operating
efficiency 


caused by mixed refrigerant, and loss of refrigerant caused 


by system rupture or irreversible contamination (e.g., mixture 


of CFC-12 and HCFC-22). These types of risks impose potential 


costs upon the private parties that would purchase reclaimed 


refrigerant, and so these parties would be expected to take 


steps to ensure purity to a level adequate for the intended 


use. Equipment owners, for example, could undertake a range 


of actions to ensure adequate refrigerant purity: Purchase used 


refrigerants only from reputable suppliers or technicians, insist 


upon contract provisions specifying technician or supplier
guarantees 


to repair any equipment damaged by contaminated refrigerant, 


insist that used refrigerant meet some purity standard less 


stringent than ARI 700, or only use refrigerant that is fully 


certified to meet ARI 700.


   The degree to which the purchasers of used refrigerant would 


undertake these actions will depend upon their awareness of 


the risks posed by contaminated or mixed refrigerants. Because 


the potential damage to equipment might only occur after months 


or years of operation, consumer awareness of the risks could 


trail actual equipment damage. This problem of inadequate
information 


could, however, be addressed through EPA and industry efforts 


to educate potential consumers of refrigerants. EPA solicits 


public comment on the adequacy of the private party actions 


described above and potential EPA and industry educational efforts 


in minimizing the harm that may result from damage to private 


equipment from contaminated or mixed refrigerants.


   Some members of the STOPAC subcommittee for recycling suggested 


that EPA address cross-contamination concerns through a less 


stringent requirement than requiring reclamation of all refrigerant



transferred between owners. One alternative would be to require 


reclamation only when refrigerant was moved between equipment 


of different types. Such a restriction would allow contractors 


servicing a single type of equipment to consolidate and transport 


the refrigerant to their shops for "off-site" recycling. The 


contractors could then sell the refrigerant to other customers 


using the same type of equipment, but sales of recycled refrigerant



to anyone but end-users would be prohibited. This requirement 


would be especially advantageous for contractors who service 


small equipment, for instance, home unitary air conditioners 


(central air conditioning units) utilizing HCFC-22. While recycling



machines are capable of processing 50 pounds of refrigerant 


at once, the charge in home unitary air conditioners ranges 


between four and seven pounds. Thus, allowing contractors to 


consolidate refrigerant would permit them to use their recycling 


machines more efficiently than they could if they were required 


to process each owner's refrigerant separately. Moreover, because 


1-2 pounds of refrigerant is usually left behind in recycling 


equipment after each job is complete, substantial mixing occurs 


even with on-site recycling. The purity gained by allowing only 


on-site recycling may therefore not justify the additional expense 


that this option entails.


   However, although transfers of refrigerant between similar 


pieces of equipment are less likely to lead to cross-contamination 


than transfers between different types of equipment, EPA has 


several concerns about this option. First, if limited off-site 


recycling is permitted, it may be difficult to distinguish between 


legitimate and illegal use of the recycling machines. Recycling 


centers selling refrigerant to walk-in customers may find it 


easy to masquerade as contractors recycling refrigerant only 


to recharge their customer's equipment. Second, defining "types" 


of equipment within which transfers of refrigerant could proceed 


may present problems. Should distinctions be based on size, 


possession of hermetic vs. open-drive compressors, or some other 


characteristic? Third, there is no industry standard for the 


ability of recycling machines to clean refrigerant. While the 


ARI 740 Standard for Recycling Equipment includes a test for 


cleaning ability, it does not set any minimum level of performance 


in this area. Thus, there is currently no guarantee that an 


individual recycling machine is capable of removing even those 


contaminants, such as acid and water, that recycling machines 


are theoretically capable of removing. In the future a "clean-


up" standard may be developed; with EPA's encouragement, ARI 


has taken preliminary steps in this direction. If and when such 


a standard is developed, EPA will view off-site recycling with 


more confidence.


   EPA requests comment on the option of permitting limited 


off-site recycling. Could the Agency design its program in such 


a way as to prevent the development of "Recycling centers" that 


do not analyze the refrigerant they sell? How? What criteria 


would EPA use to distinguish between equipment types? Finally, 


should even limited off-site recycling be permitted in the absence 


of a "clean-up" standard for recycling equipment?


   Some members of the STOPAC argued that EPA should allow sales 


of recycled (as opposed to reclaimed and therefore, chemically 


analyzed) refrigerant as long as the refrigerant is labelled 


as such. However, since the label would only indicate that the 


refrigerant had been used, not what its chemical contents were, 


EPA does not believe that a labelling requirement would
sufficiently 


inform the purchaser of refrigerant of the risks associated 


with its use. This rule will dramatically increase the volume 


of used refrigerant on the market, and many purchasers will 


not be familiar with the hazards that may be associated with 


used refrigerants that have not been analyzed, e.g., residuals 


from hermetic motor burnouts, improper identification,
incompatibility 


of lubricants, etc. Thus, EPA believes that the integrity of 


the market for used refrigerant is best served by requiring 


that the purity of the refrigerant be chemically verified before 


refrigerant is sold to a new owner.


   Refrigerant that is not sold to a new owner would not have 


to meet any standard of purity under section 608. When refrigerant 


is returned to the equipment from which it is removed, it is 


frequently not necessary either to test or to treat the
refrigerant. 


ASHRAE Guideline 3-1990 states, "refrigerant withdrawn from 


equipment so that routine service or major overhaul can be
performed 


can usually be returned to the equipment without reprocessing," 


and this guidance was confirmed by several members of the STOPAC 


Subcommittee for Recycling. As long as recovered refrigerant 


does not change hands, therefore, EPA considers it reasonable 


to leave treatment to the discretion of the service technician.


   4. RCRA Regulations Regarding the Management of CFCs and 


CFC-Contaminated Wastes. This section is intended to give an 


overview of EPA's hazardous waste regulations as they affect 


refrigerant recovery, recycling, and reclamation. Throughout 


this section the terms recovery, recycling, and reclamation 


are used as defined previously in section III.D. of today's 


proposed rule and not as defined in the Resource Conservation 


and Recovery Act (RCRA).{1} The regulations described in this 


section are not part of this rulemaking. Individuals with questions



regarding them should call the RCRA Hotline at 1-800-424-9346 


or 701-920-9810. 


      ³{1} As stated in RCRA regulations, material is
"recycled" 


      ³if it is used, reused, or reclaimed (40 CFR
261.1(c)(7). 


      ³A material is "used or reused" if it is either employed



      ³as an ingredient (including use as an intermediate) in 


      ³an industrial process to make a product or employed in 


      ³a particular function or application as an effective 


      ³substitute for a commercial product (40 CFR
261.1(c)(5)). 


      ³A material is "reclaimed" if it is processed to recover



      ³a usable product, or if it is regenerated (40 CFR
261.1(c)(4)). 


   a. Refrigerants. Due to a previous rulemaking (see 56 FR 


5910, February 13, 1991) and the July 28, 1989, Federal Register 


notice clarifying the applicability of RCRA Subtitle C regulations 


to CFC refrigerants (54 FR 31335), used CFC refrigerants from 


totally enclosed heat transfer equipment, including mobile air 


conditioning systems, mobile refrigeration, and commercial and 


industrial air conditioning and refrigeration systems that use 


chlorofluorocarbons as the heat transfer fluid in a refrigeration 


cycle are not hazardous wastes provided the refrigerant is recycled



or reclaimed for further use. If these CFCs are not recycled 


or reclaimed, it is the generator's responsibility to test the 


waste or apply knowledge of the waste to determine whether the 


waste exhibits a characteristic of hazardous waste (see 40 CFR 


Part 262 for standards applicable to generators of hazardous 


waste, especially 40 CFR 262.11, "Hazardous waste determination"). 


In the July 28, 1989, notice, EPA concluded that, in circumstances 


where something outside the realm of normal practice may cause 


a CFC refrigerant to exhibit a characteristic (e.g., compressor 


burnout), generators may need to determine, using testing or 


knowledge, whether the waste is hazardous. EPA was concerned 


that CFCs may break down at high compressor temperatures, forming 


hydrochloric acid, and may exhibit the characteristic of
corrosivity. 


If the spent refrigerant is mixed with a listed or characteristic 


hazardous waste (e.g., degreasing fluid or solvent), then the 


mixture may also be hazardous. 


   b. Byproducts of Refrigerant Recovery and Recycling. Two 


of the byproducts of refrigerant recovery and recyling may be 


hazardous waste: Used oil and used replaceable core filter driers. 


Generators of single and multiple pass through devices such 


as replaceable core filter-driers are subject to the RCRA hazardous



waste determination requirement (40 CFR 262.11). If the generator 


determines that the spent pass through device is a hazardous 


waste, then it must be managed in accordance with RCRA Subtitle 


C requirements. 


   As part of the CFC recycling process, used oil is separated 


from the CFCs. Used oils that are removed from refrigeration 


units and that are contaminated with CFCs are exempt from the 


rebuttable presumption of mixing with hazardous waste. The
rebuttable 


presumption of mixing, however, applies to used oil contaminated 


with CFCs that have been mixed with used oil from processes 


other than refrigeration units. (See 40 CFR 279.10(b)(ii)(B) 


and 40 CFR 279.44(c)(2). Thus, generators of used oil that is 


contaminated with CFCs from refrigeration units may wish to 


keep this oil separate from other used oil and retain records 


documenting the source of the oil. (Such recordkeeping, however, 


is not required.)


   Used oil separated from CFCs during refrigerant recycling 


is subject to the newly finalized part 279 requirements for 


recycled used oil management standards (57 FR 41566, September 


10, 1992). If used oil is destined for disposal, the generator 


has the responsibility to test or apply knowledge to determine 


whether the used oil exhibits one or more of the characteristics 


of hazardous waste. (See 40 CFR part 279, subpart I, Standards 


for use as a Dust Suppressant and Disposal of Used Oil.)


   Used oils that remain after the CFC recovery step and that 


are recycled are subject to 40 CFR part 279 requirements as 


applicable. Under RCRA subtitle C regulations, used oil that 


is recycled by being burned for energy recovery is subject to 


40 CFR part 266, subparts E and H. The 40 CFR part 266, subpart 


E requirements are included in new part 279 of 40 CFR. (See 


40 CFR part 279, subparts B, G, and H.)


   (1) Used Oil Fuel Specifications. Used oil that fails to 


meet used oil fuel specifications in the new 40 CFR 279.11 and 


279.60(c) (current 40 CFR 266.40(e){2}) may be burned only in 


industrial boilers and furnaces, as defined in 40 CFR 261.10 


and 266.41(b). Under the new 40 CFR 279.63(b) (current 40 CFR 


266.40)c)), used oil to be burned for energy recovery that contains



more than 1,000 ppm of total halogens is presumed to be hazardous 


waste because it has been mixed with halogenated hazardous waste 


listed in 40 CFR part 261, subpart D (e.g., F001, which includes 


chlorinated fluorocarbons used as solvents). Used oil that contains



greater than 1,000 ppm total halogens for which the presumption 


cannot be rebutted or used oil for which the generator chooses 


not to rebut the presumption is subject to regulation under 


subpart H of 40 CFR part 266, Hazardous Waste Burned in Boilers 


and Industrial Furnaces. The presumption may be rebutted by 


showing that the used oil does not contain concentrations in 


excess of 1,000 ppm of halogenated hazardous constituents listed 


in 40 CFR part 261, appendix VIII or that the constituents are 


only hazardous waste generated by conditionally exempt small 


quantity generators subject to 40 CFR 261.5.


      ³{2} Used oil that exceeds any of the following
specification 


      ³levels is considered to be "off-specification" used oil



      ³under 40 CFR 266.40(e): Arsenic-5 ppm, Cadmium-2 ppm, 


      ³Chromium-10 ppm, Lead-100 ppm, Flash Point-100øF
minimum, 


      ³Total Halogens-4000 ppm.


   Appendix VIII of 40 CFR part 261 identifies CFCs used as 


solvents as a hazardous constituent. Thus, a chemical analysis 


may indicate that used oil containing a spent CFC (in
concentrations 


exceeding 1,000 ppm) used as a refrigerant (rather than as a 


solvent), is a hazardous waste under the rebuttable presumption 


at 40 CFR 279.11 and 279.60(c), (current 40 CFR 266.40(e)) when, 


in fact, the CFCs are not derived from a listed hazardous waste. 


Demonstrating that the CFCs in the used oil result from a
refrigerant 


use rather than from mixture with a listed hazardous waste may 


rebut the presumption. Once used oil from refrigeration units 


is mixed with used oil from other sources, one way to rebut 


the presumption could be to maintain records of chemical analysis 


for each generated wastestream, although EPA does not require 


this chemical analysis and recordkeeping. Then, non-refrigerant 


wastestreams containing CFCs could be eliminated from acceptance 


for commingling with used oil destined for burning for energy 


recovery as a used oil fuel.


   (2) Used Oil Fired Space Heaters. As discussed in 40 CFR 


278.23 (a) and 40 CFR 279.62 (a) and (b) (current 40 CFR
266.44(b)), 


owners and operators of used oil-fired space heaters that burn 


used oil fuel under the provisions of 266.41(b)(2) are exempt 


from notification requirements of Section 3010 of RCRA. Off-


specification used oil fuel may be burned for energy recovery 


in used oil-fired space heaters provided that: the heater burns 


only used oil that the owner or operator generates or used oil 


received from do-it-yourself oil changers who generate used 


oil as household waste; the heater is designed to have a maximum 


capacity of not more than 0.5 million Btu per hour; and the 


combustion gases from the heater are vented to the ambient air. 


For example, the generator could be the owner of the refrigeration 


equipment as well as the service person or company who, in
servicing 


the equipment, collects the used oil. Than, the service person 


or company may burn the used oil provided that the owner or 


operator can successfully rebut the presumption at 40 CFR 279.66(a)



(current 40 CFR 266.40(c)).


   c. Refrigerant Reclamation. Used oil separated from CFCs 


during reclamation is managed in the same manner as used oil 


separated from CFCs during recycling (see Refrigerant Recycling 


section). The generator has the responsibility to determine 


whether residuals (including used oil) generated during reclamation



are hazardous. If the residuals consist of a mixture of CFCs, 


used as refrigerants, and other solvents listed in 40 CFR part 


261, subpart D, then the residuals from CFC reclamation would 


be a listed hazardous waste (see 40 CFR 261.3(a)(2)(iii)). If 


the residuals from CFC reclamation exhibit one or more of the 


characteristics of hazardous waste, then the residuals are a 


characteristic hazardous waste (see 40 CFR part 261, subpart 


C).


   d. Used Refrigerant Oil. Thus far, this portion of the preamble 


has provided an overview of RCRA regulations with respect to 


refrigerant CFCs that have been recovered or will be recycled 


or reclaimed. Used oils, drained from refrigeration units, will 


be subject to the same regulations discussed above for used 


oils separated from CFCs during recycling and reclamation. For 


an additional discussion of regulations applicable to used oil 


and used oil filters, see 57 FR 21524, May 20, 1992.


   5. Handling Multiple Refrigerants in Recycling and Recovery 


Equipment. Under ordinary circumstances, one to two pounds of 


refrigerant may be left behind in a recycling or recovery device 


after the device is discharged back into the original equipment 


or into another container. Unless it is removed from the recovery 


or recycling machine using special methods, this refrigerant 


will contaminate the next batch of refrigerant recovered by 


the machine. If the first and second refrigerants are different 


(e.g., HCFC-22 and CFC-12), this mixture will become unusable, 


and will have to be disposed of.


   EPA requests comment on whether or not it should require 


technicians to remove residual refrigerant from recycling and 


recovery machines when these machines are switched between
refrigerants. 


Methods that may be used to remove residual refrigerant include 


evacuation using a second recovery device, heating the condenser 


of the recovery or recycling machine using a heat gun, or cooling 


the container (and/or tubing to it) to which the recovery or 


recycling machine is evacuated. Another option that would prevent 


mixture of refrigerants would be to require separate condensers 


for each refrigerant on recovery or recycling machines intended 


for use with multiple refrigerants. This, however, would increase 


the cost of the recovery or recycling machines. EPA requests 


comment on the effectiveness and practicality of procedures 


for evacuating refrigerants from recycling and recovery devices. 


G. Certification of Recycling and Recovery Equipment 


   In order to ensure that recycling and recovery equipment 


on the market is capable of limiting emissions of CFCs and HCFCs, 


EPA is proposing that recovery and recycling equipment manufactured



or imported on or after [6 months after publication of the final 


rule], be tested and certified by an EPA-approved laboratory 


or organization. The Agency proposes to require verification 


of performance in two areas that affect total recovery efficiency: 


(1) Vapor recovery efficiency and (2) efficiency of noncondensable 


purge devices on recycling machines. In addition, EPA is proposing 


to require that equipment and hoses be fitted with shutoff valves 


or low-loss fittings. 


   In addition to the initial testing, manufacturers would have 


to have their equipment models tested or inspected at least 


once every three years to ensure that no changes had been made 


to the design that might prevent the equipment from meeting 


EPA requirements. Such "follow-up" programs are standard in 


equipment testing programs throughout industry. Manufacturers 


and importers would also have to place a label on each piece 


of certified equipment indicating that it is certified and showing 


which organization tested and certified it. This label would 


inform both consumers (technicians) and EPA enforcement personnel 


that the equipment met EPA standards.


1. Standards for Recovery and Recycling Machines Intended for 


Use With Air Conditioning and Refrigeration Equipment Except 


Small Appliances


   a. Recovery efficiency. In developing proposed levels of 


evacuation, EPA has considered the technical capabilities, ease 


of use, and costs of recycling and recovery equipment, the
servicing 


times that would be necessary to achieve different vacuums, 


and the amounts of refrigerant that would be released under 


different evacuation requirements and their predicted impact 


on the ozone layer (and therefore, on human health and the
environment). 


The Agency has attempted to evaluate these factors in both the 


short and the long term, considering the capabilities of both 


existing and possible future equipment. Often the factors are 


interrelated; for instance, more powerful recovery and recycling 


machines are often more expensive, but they also reduce the 


time that the technician must spend evacuating the system.


   The relationship between the depth of vacuum drawn and the 


percentage of refrigerant that is recovered by recycling or 


recovery equipment varies from refrigerant to refrigerant. For 


HCFC-22, a vacuum of approximately 9 inches of mercury must 


be drawn in order to recover 99 percent of the refrigerant in 


the system. For CFC-12, vacuum of approximately 17 inches must 


be drawn to recover 99 percent of the refrigerant. For low-pressure



refrigerants, such as CFC-11 and HCFC-123, much deeper vacuums 


must be drawn in order to achieve 99 percent recovery; for
instance, 


a vacuum of 28 inches must be achieved in order to recover 99 


percent of the CFC-11 in a system.


   EPA surveyed manufacturers of recovery and recycling machines 


in order to ascertain the technical capabilities, prices, and 


availability of the equipment. Recycling and recovery machines 


can be divided into six major categories, depending upon the 


type of air conditioning or refrigeration equipment that they 


are intended to service. These categories include recovery or 


recycling machines intended to service: (1) Small appliances 


(discussed in section III.F.2 below), (2) high-pressure equipment 


with a charge of less than 50 pounds (e.g., residential and 


light commercial air conditioning), (3) high-pressure equipment 


with a charge of more than 50 pounds, (4) intermediate pressure 


equipment, (5) low-pressure equipment and (6) very high pressure 


equipment. Each of these categories varies in price and ability 


to draw vacuum. In addition, portability is of steadily lessening 


importance as one moves from the first to the fifth categories.


   EPA's survey indicated that currently available recovery 


and recycling machines intended for use with small high-pressure 


equipment are capable of drawing vacuums of between 9.9 and 


29.8 inches of Hg vacuum. The more efficient equipment appears 


to be competitively priced; while models drawing approximately 


10 inches of mercury ranged in price between $4,180 and $17,493, 


models drawing over 29 inches of mercury ranged in price between 


$1,316 and $6,700 (RIA). (The price of recovery and recycling 


machines appears to depend more on recovery rates, capacity, 


and number of refrigerants handled than on recovery efficiency.)


   However, the survey showed that the more efficient equipment 


probably could not be available in large quantities by the time 


the equipment certification requirements become effective. This 


result has been confirmed by a number of representatives of 


industry on the STOPAC Subcommittee for Recycling, who have 


stated that most models of recovery and recycling machines
currently 


on the market are incapable of drawing more than 10 inches of 


vacuum without risking damage to the machine's compressor.
According 


to these representatives, the relatively light, small recovery 


and recycling machines intended for use with small high pressure 


systems usually have hermetic compressors, which tend to overheat 


when drawing deep vacuums. This equipment also has difficulty 


working against the large difference in pressures (compression 


ratio) that must be overcome in order to achieve deeper vacuums. 


Thus, EPA is proposing to require that recovery or recycling 


machines intended for use with small high-pressure systems are 


able to draw a 10-inch vacuum.


   Some industry representatives have stated that most recovery 


or recycling machines currently available would have difficulty 


drawing more than a 4-inch vacuum on equipment using HCFC-22, 


because compression ratios at deeper vacuums become quite large 


for HCFC-22. The Agency requests comment on the alternative 


of requiring recovery or recycling machines intended for use 


with small systems using HCFC-22 to draw a 4-inch vacuum. EPA 


is willing to consider a less stringent standard for recycling 


and recovery machines used with small systems utilizing HCFC-


22 not only because of technical limitations but because HCFC-


22 has only approximately five percent of the ozone-depletion 


potential of CFC-11 and CFC-12.


   If more efficient equipment becomes widely available, EPA 


may evaluate the need for a higher standard for small, high-


pressure equipment in the more distant future. EPA requests 


comment on the possible future availability of portable, cost-


effective recovery and recycling machines able to draw more 


than 10 inches of vacuum and the costs of requiring such equipment.



Not only does EPA's survey indicates that the technology exists, 


but some industry members have stated that recovery and recycling 


machines utilizing open-drive, two-stage compressors would be 


able to achieve deep vacuums without significantly compromising 


portability or increasing cost.


   Recovery and recycling machines used to evacuate larger high-


pressure systems are capable of drawing vacuums of between 15 


and 29 inches, according to EPA's survey. These machines are 


typically larger and more powerful than machines used with
residential 


equipment because larger charge sizes necessitate both higher 


recovery rates and higher recovery efficiencies. In addition, 


portability is of somewhat less importance for large commercial 


than for residential applications because technicians in large 


commercial applications are less likely to have to carry recycling 


and recovery equipment up ladders and through narrow doorways. 


Because EPA's survey indicated that the majority of equipment 


currently available in this application draws vacuums closer 


to 20 inches than to 29 inches, EPA is proposing to require 


equipment in this application to draw a vacuum of 20 inches. 


EPA requests comment on this proposal and on the current and 


future availability of recovery or recycling machines intended 


for use with large high pressure equipment that can draw vacuums 


of more than 20 inches. As with recovery and recycling machines 


intended for use with smaller equipment, EPA may consider setting 


a stricter standard for recovery and recycling machines used 


with large equipment in the future.


   EPA's survey indicated that recovery and recycling machines 


used to service low-pressure centrifugal chillers are capable 


of drawing vacuums between 25.5 and 29.8 inches. The survey 


examined equipment in the two most common capacities for this 


application, 1,600 pounds and 3,400 pounds. For both the 1,600 


and 3,400 pound capacities, the most efficient equipment is 


somewhat more expensive than the least efficient equipment; 


however, in both cases it possesses other features besides high 


efficiency that are probably important to price (e.g., a high 


horsepower motor and a high recovery rate). More important, 


the social costs avoided by using the more efficient equipment 


(i.e., the damage to human health and the environment that would 


be caused by refrigerant released by the less efficient equipment) 


outweigh the price difference (Regulatory Impact Analysis). 


Thus, EPA is proposing to require that recovery or recycling 


machines intended for use with low pressure equipment reduce 


the system pressure to 25 mm of Hg (generally equivalent to 


a vacuum of 29 inches). EPA requests comment on this proposed 


level of evacuation.


   EPA considered defining low-pressure equipment to include 


equipment utilizing CFC-114, but the physical characteristics 


and special applications of this refrigerant appear to justify 


a separate classification, "intermediate pressure equipment." 


CFC-114 has a vapor pressure between those of low-pressure
refrigerants 


and those of high-pressure refrigerants. At a given level of 


evacuation, therefore, a higher percentage of 114 is recovered 


than would be recovered of CFC 11. Evacuation to 25 inches of 


Hg vacuum represents recovery of over 99% of the refrigerant 


in a 114 chiller. EPA is therefore proposing that CFC-114 and 


other intermediate pressure refrigerants (e.g., blends of CFCs-


114 and -12) be evacuated to 25 inches of vacuum. The Agency 


requests comment on this proposal.


   The requirements described above for high-pressure equipment 


would apply to equipment utilizing refrigerants 12, 22, 500, 


and 502. Refrigerants 13 and 503 are used in very low temperature 


applications and have very high pressures at ambient temperatures 


(e.g., 500 psia at 75 degrees F). Evacuating these refrigerants 


to the vacuums proposed for high pressure refrigerants would 


require recycling and recovery equipment to work against very 


high compression ratios, and over 99% of a very high pressure 


refrigerant can be recovered by evacuating it to atmospheric 


pressure. Thus, the standards and equipment appropriate for 


the recovery and recycling of the high pressure refrigerants 


are not appropriate for very high pressure refrigerants. ARI 


has recommended that EPA require evacuation of R-13 and 503 


to atmospheric pressure (At 75 degrees F), and EPA is proposing 


to adopt this recommendation. ARI has also noted that an especially



strong recovery container will be needed to recover these very 


high pressure refrigerants. EPA requests comment on the procedures,



equipment, and level of evacuation appropriate for recovering 


or recycling very high pressure refrigerants. 


   Following is a table listing the evacuation levels that must 


be achieved by the various types of recovery and recycling
equipment.





      Table 2.-Levels of Evacuation Which Must Be Achieved by
Recovery or     


  Recycling Machines Intended for Use With Air Conditioning or
Refrigeration  


                                   Equipment                       
          


                         [Except for Small Appliances]             
          


   [Manufactured on or after (6 months after publication of the
final rule)]  


                                                                   
          


ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÂÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ


 Type of air conditioning or refrigeration equipment with  ³  
 Inches of     


which recovery or recycling machine is intended to be used ³  
  vacuum       


ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÅÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ


                                                           ³  
               


High Pressure Equipment with a Charge of Less than 50      ³
10               


 Pounds.                                                   ³  
               


High Pressure Equipment with a Charge of More than 50      ³
20               


 Pounds.                                                   ³  
               


Very High Pressure Equipment.............................. ³ 0
               


Intermediate Pressure Equipment........................... ³
25               


Low-pressure Equipment.................................... ³
25 mm Hg         


ÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÁÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄÄ





   A few types of recycling and recovery equipment do not use 


an on-board compressor to remove refrigerant from the air
conditioning 


or refrigeration equipment. One model that has been brought 


to EPA's attention relies on the system compressor to evacuate 


the refrigerant, similar to the passive recovery devices used 


to evacuate refrigerators and freezers (discussed below). Another 


model uses an inert gas to push refrigerant out of the system 


and into the recovery device. EPA requests comment on how to 


evaluate the recovery efficiency of these two and other possible 


devices.


   The Agency is concerned that it would not be possible to 


ensure the performance of the first type of equipment because 


that performance would depend upon the system compressor, which 


would vary from job to job. The worst case would arise when 


the system compressor was not operating at all, in which case 


the efficiency of the equipment would probably be quite low. 


Although the technician in such a situation could theoretically 


return to his shop to pick up a recovery or recycling machine 


with an on-board compressor, EPA is concerned that this process 


would prove too time-consuming to depend upon in practice. EPA 


requests comment on these issues.


   Because the second type of equipment does not depend upon 


any external equipment during the recovery process, it should 


be possible to use laboratory tests to gauge its recovery
efficiency 


in the field. One method of measuring the efficiency might be 


to use a mass-balance approach, weighing the recovery equipment 


and the air conditioning or refrigeration equipment before and 


after the recovery procedure and subtracting the mass of the 


introduced inert gas. Such a method would require that the
refrigerant 


be distinguishable from the inert gas. EPA could approve the 


equipment if it achieved at least the recovery efficiency of 


comparable compressor-bearing equipment (between 98.5-99.5%). 


Although EPA is not proposing this method at this time, the 


Agency requests comment on this method of ensuring the recovery 


efficiency of this and other types of recovery or recycling 


equipment.


   b. Refrigerant recovery rates. Some representatives of industry 


on the STOPAC Subcommittee for Recycling have encouraged EPA 


to set minimum standards for liquid and vapor recovery rates, 


arguing that technicians will be less tempted to interrupt a 


swift recovery than a slow one (Letter from Bruce Siebert, the 


Trane Company, to Deborah Ottinger, Office of Air and Radiation, 


August 14, 1991). EPA is not proposing minimum recovery rates 



as a lead option in today's proposed rule. The Agency believes 


that, given the proposed requirements for evacuation and the 


growing value of refrigerant, contractors and technicians have 


sufficient incentive to purchase equipment with recovery rates 


adequate for their needs. However, EPA requests comment on the 


need for minimum recovery rates and on what those recovery rates 


might be for different types of air conditioning and refrigeration 


equipment.


   c. Low loss fittings. Low loss fittings or positive shutoff 


connections prevent refrigerant from escaping from hoses and 


equipment during connection and disconnection of recovery and 


recycling machines. EPA analysis indicates that shutoff valves 


for both high-pressure and low-pressure systems are cost-effective,



and in the case of low-pressure systems, actually save the user 


money (RIA). EPA is therefore proposing to require that hoses 


on recovery and recycling machines be equipped with low loss 


fittings. EPA requests comment on this proposal.


   d. Purge loss. Most recycling machines (but not recovery 


machines) are equipped with air purge devices, wh