Indoor airPLUS Construction Specifications
Office of Air and Radiation (6609J) EPA 402/K-08/003, January 2009
Contents
About the Indoor airPLUS Construction Specifications
These specifications were developed by the U.S. Environmental Protection Agency (EPA) to recognize new homes equipped with a comprehensive set of Indoor Air Quality (IAQ) features. They were developed with significant input from stakeholders, based on best available science and information about risks associated with IAQ problems, and balanced with practical issues of cost, builder production process compatibility, and verifiability. Although these measures were designed to help improve IAQ in new homes compared with homes built to minimum code, they alone cannot prevent all IAQ problems. Occupant behavior is also important. For example, smoking indoors would negatively affect IAQ and the performance of the specified Indoor airPLUS measures.
Qualified homes earn the Indoor airPLUS label. Place it next to the ENERGY STAR label.

How to Qualify a Home for the Indoor airPLUS Label
Homes that comply with these specifications and are verified with a completed Indoor airPLUS Verification Checklist can use Indoor airPLUS as a complementary label to ENERGY STAR for New Homes. Only ENERGY STAR qualified homes are eligible for this label. Verification can be completed during the ENERGY STAR inspection process, and must be conducted in accordance with Residential Energy Services Network (RESNET) Standards by a RESNET-accredited provider and must meet all applicable codes. Instructions for Indoor airPLUS verification are listed below in the Verification Checklist.
- Read the Labeling and Reporting Instructions
Terms Used in This Document
- EXCEPTIONS to the requirements described in these construction specifications are noted as appropriate. For climate exceptions, refer to the 2006 International Energy Conservation Code (IECC)
Climate Zone map (Figure 301.1). Climate Zone names may include a number for the temperature zone and a letter for the moisture zone (e.g., Zone 3C refers to coastal California only).
- NOTES provide additional information to clarify specification requirements.
- ADVISORIES provide additional guidance to be considered, but are not specification requirements.
- ABBREVIATIONS and
REFERENCES used in these specifications.
- PERFORMANCE TEST ALTERNATIVES describe alternate compliance approaches where performance testing is practical and results are comparable to those of the prescriptive best practices required in the specification.
Indoor airPLUS Verification Checklist
Indoor airPLUS Verification Checklist
This stand-alone checklist provides the requirements for building an Indoor airPLUS qualified home.
Click on the image to view, download and print a full 2-page version of the checklist.
Guidance for Completing the Indoor airPLUS Verification Checklist:
- Only ENERGY STAR qualified homes verified to comply with these specifications can earn the Indoor airPLUS label. See Indoor airPLUS Construction Specifications for full descriptions of the requirements, terms, exceptions, abbreviations, references, and climate map used in this checklist. Verification is not complete until this checklist is completed in full and signed.
- Check one box per line. Check “N/A” for specifications that do not apply for specific conditions (e.g., climate) according to the Exceptions described in the Indoor airPLUS Construction Specifications. Check either “Builder” or “Rater” for all other items to indicate who verified each item. Items may be verified visually on site during construction, by reviewing photographs taken during construction, by checking documentation, or through equivalent methods as appropriate. If using a performance testing alternative to meet requirement
4.2 or 4.4, the box marked “Tested” must be checked and testing documentation must be pro-vided in the Home Energy Rating System/Builder Option Package (HERS/BOP) file.
- The rater who conducted the verification, or a responsible party from the rater’s company, must sign the completed verification checklist. The builder must sign the checklist if any items in the “Builder” column are checked, and by so doing accepts full responsibility for verifying that those items meet Indoor airPLUS requirements.
- The builder provides one copy of the completed and signed checklist for the buyer. The HERS/BOP provider or rater files a copy with HERS/BOP and ENERGY STAR documentation (e.g., Thermal Bypass Checklist) for the home.
- The checklist may be completed for a batch of homes using a RESNET-approved sampling protocol when qualifying homes as ENERGY STAR. For example, if the approved sampling protocol requires rating one in seven homes, then the checklist will be completed for the one home that was rated.
Note: The Indoor airPLUS Construction Specifications are designed to help improve indoor air quality (IAQ) in new homes compared with homes built to minimum code. These measures alone cannot prevent all IAQ problems; occupant behavior is also important. For example, smoking indoors would negatively impact a home’s IAQ and the performance of the specified Indoor airPLUS measures.
1. Moisture Control
Note:
ENERGY STAR Thermal Bypass Checklist (TBC) requirements are an integral part of the Indoor airPLUS moisture control strategy. TBC requirements improve the control of air and thermal flows through building assemblies, which is critical to controlling water vapor migration and condensation. Since TBC compliance and verification are required for ENERGY STAR qualification, TBC requirements are not re-stated in the Indoor airPLUS Construction Specifications.
Water-Managed Site and Foundation
| 1.1 | Provide site and foundation drainage as follows:
|
| 1.2 | Install capillary breaks as follows: Beneath concrete slabs, including basement floors:
Crawlspace floors:
Exceptions:
|
| 1.3 | Damp-proof or waterproof exterior surfaces of below-grade foundation walls as follows:
Exceptions: |
| 1.4 | Insulate and condition basements and crawlspaces as follows:
Exceptions:
Note: |
Water-Managed Wall Assemblies
| 1.5 | Install a continuous drainage plane behind exterior wall cladding, AND install flashing or an equivalent drainage system at the bottom of exterior walls to direct water away from the drainage plane and foundation. Drainage plane material shall overlap flashing and shall be fully sealed at all penetrations. Any of the following systems meet this requirement:
Note: |
| 1.6 | Fully flash all window and door openings, including pan flashing at sills, side flashing that extends over pan flashing, and top flashing that extends over side flashing. |
Water-Managed Roof Assemblies
| 1.7 | Direct roof water away from the house using gutters and downspouts that empty into lateral piping that deposits water on a sloping finish grade a minimum of 5 ft. from the foundation. Roofs designed without gutters are acceptable if they are designed to deposit rainwater to a grade-level rock bed with waterproof liner and drain pipe that deposits water on a sloping finish grade, as specified above. When lot space limits or prevents required grading, direct roof water to an underground catchment system (not connected to the foundation drain system) that deposits water a minimum of 10 ft. from the foundation. Rainwater-harvesting systems may be used to meet this requirement when they are designed to properly drain overflow, meeting discharge-distance requirements above.
Exception: |
| 1.8 | Fully flash roof/wall intersections and all roof penetrations. Install step flashing at all roof/wall intersections, except metal and rubber membrane roofs, where continuous flashing should be installed. “Kick-out” flashing shall be installed at the low end of roof/wall intersections to direct water away from walls, windows, and doors below. In all cases, flashing shall extend at least 4 in. on the wall surface above the roof deck and shall be integrated with the drainage plane above (shingle style) to direct water onto and not behind flashing. In addition, intersecting wall siding should terminate a minimum of 1 in. above the roof, or higher according to the manufacturer’s recommendations. |
| 1.9 | Install self-sealing bituminous membrane or the equivalent at all valleys and roof decking penetrations for durability at potential failure points.
Exception: |
| 1.10 | In colder climates (IECC Climate Zones 5 and higher), install self-sealing bituminous membrane or the equivalent (“ice flashing”) over the sheathing at eaves to provide protection from ice dams. The ice flashing shall extend up the roof plane from the eave to a point at least 2 ft. inside the vertical plane of the exterior wall.
Exception: |
Interior Water Management
| 1.11 | Install moisture-resistant materials and moisture-protective systems in vulnerable areas. For example:
|
| 1.12 | Do not install continuous vapor barriers on the interior side of exterior walls that have high condensation potential (e.g., below-grade exterior walls in most climates and above-grade exterior walls in warm-humid climates). For the purpose of this specification, vapor barriers are materials that have a perm rating of 0.1 or less (see manufacturer’s product specifications or 2005 ASHRAE Handbook of Fundamentals, Chapter 25, Tables 7A and 7B). |
| 1.13 | Do not install building materials that have visible signs of water damage or mold. In addition, interior walls shall not be enclosed (e.g., with drywall) if either the framing members or insulation has a high moisture content. For wet-applied insulation, follow the manufacturer’s drying recommendations.
Advisory: |
2. Radon Control
| 2.1 | Homes built in EPA Radon Zone 1
(see
www.epa.gov/radon/zonemap.html) shall be constructed with approved radon-resistant features according to EPA's
"Building Radon Out"; NFPA 5000, Chapter 49; IRC, Appendix F; CABO, Appendix F; or ASTM E1465.
The following requirements shall be verified:
Exception: Advisories:
|
| 2.2 | Provide two radon test kits designed for 48-hour exposures for the buyers of homes in EPA Radon Zones 1 and 2, including test kit instructions and EPA guidance on follow-up actions to be taken in response to the test results.
Advisory: |
3. Pest Barriers
| 3.1 | Minimize pathways for pest entry by sealing penetrations and joints in and
between the foundation and exterior wall assemblies with blocking materials,
foam, and polyurethane caulk or the equivalent. Sump pit covers shall be air
sealed (e.g., mechanically attached with full gasket seal or the equivalent).
Advisories:
|
| 3.2 | Provide corrosion-proof rodent/bird screens (e.g., copper or stainless steel mesh) for all building openings that cannot be fully sealed and caulked (e.g., ventilation system intake/exhaust outlets and attic vent openings). This requirement does not apply to clothes dryer vents. |
4. HVAC Systems
| 4.1 | Heating and cooling design loads shall be determined for each room
according to ACCA Man J, ASHRAE Handbooks, or equivalent software. Heating and cooling equipment shall be properly sized and selected to meet the design loads and accommodation must be made for pressure drop from specified filter (see Specification
4.7). This requirement shall be met by an ENERGY STAR HVAC QI Certificate (where available) OR verification of all the following:
|
| 4.2 | Duct system(s) shall be designed according to ACCA Man D, ASHRAE Handbooks, or equivalent software AND installed to be substantially airtight, properly balanced, and protected from construction debris. This requirement shall be met by an ENERGY STAR HVAC QI Certificate (where available) OR verification of all the following prescriptive requirements, OR the Performance Test Alternative below:
Performance Test Alternative:
|
| 4.3 | No air-handling equipment or ductwork shall be located in garages.
Note: |
| 4.4 | Room pressure differentials shall be minimized by installing transfer grilles
or jump ducts for any closed room that does not have a dedicated return, except
for baths, kitchens, closets, pantries, and laundry rooms. The opening size
shall be 1 square in. capacity (grille area) per cfm of supply (including free area undercut below door as part of the area).
Performance Test Alternative: |
| 4.5 | Provide mechanical whole-house
ventilation meeting all ASHRAE 62.2 requirements. The following
requirements shall be visually verified:
Note: |
| 4.6 | Provide local exhaust ventilation
to the outdoors for known pollutant sources, as follows:
|
| 4.7 | Central forced-air HVAC systems shall include a filtration system meeting the
following requirements:
Advisory:
|
| 4.8 | In “Warm-Humid” climates as defined by IECC
Figure 301.1 (i.e., Climate Zone 1 and portions of Zones 2 and 3A below the white line), equipment shall be installed with sufficient latent capacity to maintain indoor relative humidity (RH) at or below 60%.
This requirement shall be met by either:
Exception: Advisory: |
5. Combustion Pollutant Control
| 5.1 | For combustion space-heating and water-heating equipment located in
conditioned spaces:
Exception: Note: |
| 5.2 | Fireplaces and other fuel-burning space-heating appliances located in
conditioned spaces shall be vented to the outdoors and supplied with adequate
combustion and ventilation air according to the manufacturers’ installation
instructions, AND they shall meet the following energy efficiency and emissions
standards and restrictions:
Advisory: |
| 5.3 | All homes equipped with combustion appliance(s) or an attached garage shall have a carbon monoxide (CO) alarm installed in a central location in the immediate vicinity of each separate sleeping zone (e.g., in a hallway adjacent to bedrooms.) The alarm(s) shall be hard-wired with a battery back-up function and placed according to NFPA 720. The alarms shall be certified by either CSA 6.19-01 or UL 2034. |
| 5.4 | Reduce exposure to environmental tobacco smoke (ETS) in multi-family
buildings by:
|
| 5.5 | Attached garages shall be isolated from conditioned spaces as follows:
|
| 5.6 | Attached garages shall include an exhaust fan, with a minimum installed
capacity of 70 cfm, rated for continuous operation, and installed to vent directly outdoors. If automatic fan controls are installed, they shall activate the fan whenever the garage is occupied and for at least 1 hour after the garage has been vacated.
Advisory: |
6. Low-Emission Materials
Note:
The evaluation, certification, and labeling of products for indoor VOC emissions is complex and evolving. EPA has not established threshold levels for indoor VOC emissions from any of the product categories addressed in these specifications. The third-party programs referenced in these specifications include U.S. programs that are designed to reduce indoor human exposure to individual VOCs of potential concern for human health effects, compared to similar products not certified as low-VOC or no-VOC. EPA will consider modifying these specifications to include additional third-party programs as appropriate.
| 6.1 | Structural plywood, oriented strand board (OSB), and composite wood products (i.e., hardwood plywood, particleboard, medium density fiberboard [MDF], and cabinetry made with these products) shall be third-party certified for compliance with industry and federal standards, as follows:
Note: |
| 6.2 | Interior paints and finishes, including 90% or more of such products applied
to interior surfaces of homes, shall be certified low-VOC or no-VOC by one of
the following:
|
| 6.3 | Carpets and carpet adhesives shall be labeled with, or otherwise documented as meeting, the Carpet & Rug Institute (CRI) Green Label Plus or Green Label testing program criteria. Carpet cushion (i.e., padding) shall similarly be certified to meet the CRI Green Label testing program criteria. |
Abbreviations
| Term | Definition |
|---|---|
| BOP | Builder Option Package (ENERGY STAR for Homes) |
| cfm | cubic feet per minute |
| fpm | feet per minute |
| ft. | feet |
| HERS | Home Energy Rating System |
| HVAC | heating, ventilating, and air-conditioning |
| IAQ | indoor air quality |
| in. | inches |
| mil | common term to describe plastic sheeting thickness; 1 mil equals 0.001 inches |
| min. | minimum |
| MERV | Minimum Efficiency Reporting Value; defined in ASHRAE 52.2 |
| Pa | Pascals |
| QI | Quality Installation (ENERGY STAR HVAC QI) |
| s.f. | square feet |
| spec | specification |
| TBC | Thermal Bypass Checklist (ENERGY STAR for Homes) |
| VOC | Volatile Organic Compound |
| w.c. | water column |
7. Home Commissioning
| 7.1 | HVAC systems and ductwork shall
be verified to be dry and clean and installed according to their
design as documented by an ENERGY STAR HVAC QI Certificate (where available) OR as follows:
Note: |
| 7.2 | Verify that the home has been ventilated with outside air at the highest rate practical during and shortly after installing products that are known sources of contaminants (e.g., cabinets, carpet padding, and painting) and during the period between finishing and occupancy, meeting ventilation requirements for outdoor air flow and humidity control (see Specifications 4.5 and 4.8). If whole house ventilation cannot be scheduled prior to occupancy, advise the buyer to operate the ventilation system at the highest rate it can provide during the first few months of occupancy, meeting the above requirements. |
| 7.3 | Provide for buyers a completed checklist and other required documentation
about the IAQ features of their home, including:
|
References
ACCA Man D: ACCA Manual D: Residential Duct Systems. 1995. Air Conditioning Contractors of America.
ACCA Man J: ACCA Manual J: Residential Load Calculation. 2006. Air Conditioning Contractors of America.
ACCA 5 QI-2007: ANSI/ACCA Standard 5 QI-2007: HVAC Quality Installation Specification. 2007. Air Conditioning Contractors of America.
AHRI Directory: AHRI Directory of Certified Product Performance. Air-Conditioning, Heating, and Refrigeration Institute.
ANSI A208.1: ANSI A208.1: Standard for Wood Particleboard. 1999. American National Standards Institute.
ANSI A208.2: ANSI A208.2: Standard for Medium Density Fiberboard (MDF). 2002. American National Standards Institute.
ANSI/HPVA HP-1-2004: American National Standard for Hardwood and Decorative Plywood. 2004. American National Standards Institute / Hardwood Plywood and Veneer Association.
ANSI Z21.88/CSA 2.33: ANSI Standard Z21.88-2005/CSA Standard 2.33-2005: Vented Gas Fireplace Heaters. 2005. American National Standards Institute / Canadian Standards Association.
ASHRAE Handbooks: ASHRAE Handbook Series. American Society of Heating, Refrigeration, and Air-Conditioning Engineers.
ASHRAE 52.2: ANSI/ASHRAE Standard 52.2-2007: Method of Testing General Ventilation Air-Cleaning Devices for Removal Efficiency by Particle Size. 2007. American Society of Heating, Refrigeration, and Air-Conditioning Engineers.
ASHRAE 62.2: ANSI/ASHRAE Standard 62.2-2007: Ventilation and Acceptable Indoor Air Quality in Low-Rise Residential Buildings. 2007. American Society of Heating, Refrigeration, and Air-Conditioning Engineers.
ASHRAE 152: ANSI/ASHRAE Standard 152-2004: Method of Test for Determining the Design and Seasonal Efficiencies of Residential Thermal Distribution Systems. 2004. American Society of Heating, Refrigeration, and Air-Conditioning Engineers.
ASTM E1465: ASTM Standard E1465-06: Standard Practice for Radon Control Options for the Design and Construction of New Low-Rise Residential Buildings. 2006. American Society for Testing and Materials.
ASTM E1509: ASTM Standard E1509-04: Standard Specification for Room Heaters, Pellet Fuel-Burning Type. 2004. American Society for Testing and Materials. ASTM E2600: ASTM Standard E2600-08: Standard Practice for Assessment of Vapor Intrusion into Structures on Property Involved in Real Estate Transactions. 2008. American Society for Testing and Materials.
ASTM E1554: ASTM Standard E1554-03: Standard Test Methods for Determining External Air Leakage of Air Distribution Systems by Fan Pressurization. 2003. American Society for Testing and Materials.
ASTM E1602: ASTM Standard E1602-03: Standard Guide for Construction of Solid Fuel Burning Masonry Heaters. 2003. American Society for Testing and Materials.
CABO: CABO One and Two Family Dwelling Code. 1998. Council of American Building Officials.
CA Section 01350: California Section 01350: Special Environmental Requirements Specification, including Addendum 2004-1: Standard Practice for the Testing of Volatile Organic Emissions from Various Sources Using Small-Scale Environmental Chambers. 2004. State of California.
CA Title 17: California Code of Regulations, Title 17, sections 93120 - 93120.12. 2008. State of California.
CHPS List: Collaborative for High Performance Schools (CHPS) Low Emitting Materials List.
CRI Green Label: Carpet and Rug Institute Green Label Testing Programs.
CSA 6.19-01: CAN/CSA Standard 6.19-01: Residential Carbon Monoxide Alarming Devices. 2001. Canadian Standards Association.
ENERGY STAR HVAC QI: ENERGY STAR HVAC Quality Installation (pilot program). U.S. Environmental Protection Agency.
ENERGY STAR Thermal Bypass Checklist: U.S. Environmental Protection Agency.
EPA Building Radon Out: Building Radon Out: A Step-by-Step Guide On How to Build Radon-Resistant Homes. 2001. U.S. Environmental Protection Agency.
EPA Radon Maps: EPA’s Map of Radon Zones. 2008. U.S. Environmental Protection Agency.
EPA Standard for New Residential Wood Heaters: 40 CFR Part 60, subpart AAA: Standards of Performance for New Residential Wood Heaters. 1988. U.S. Environmental Protection Agency.
EPA Vapor Intrusion Primer: Brownfields Technology Primer: Vapor Intrusion Considerations for Redevelopment. 2008. U.S. Environmental Protection Agency.
EPPS CPA 3-08: Environmental Preferable Product Specification CPA 3-08. 2008. Composite Panel Association.
Greenguard Certification for Paints and Coatings: Greenguard Certification Program for Low Emitting Products: Paints and Coatings. 2005. Greenguard Environmental Institute.
Green Seal Standard GS-11: GS-11: Green Seal Environmental Standard for Paints and Coatings. 2008. Green Seal, Inc.
HUD Title 24: U.S. HUD Title 24 Part 3280: Manufactured Home Construction and Safety Standards. 1993. U.S. Department of Housing and Urban Development.
IBC: International Building Code. 2003. International Code Council, Inc.
IECC: International Energy Conservation Code. 2006. International Code Council, Inc.
IRC: International Residential Code for One- and Two-Family Dwellings. 2006. International Code Council, Inc.
KCMA ESP 01-06: Environmental Stewardship Certification Program. 2006. Kitchen Cabinet Manufacturer’s Association.
MPI GPS-1 and GPS-2: Master Painters Institute (MPI) Green Performance Standards for Paints and Coatings [GPS-1 and GPS-2]. 2008. Master Painters Institute, Inc.
NFPA 54: National Fuel Gas Code. 2006. National Fire Protection Association.
NFPA 720: Standard for the Installation of Household Carbon Monoxide (CO) Warning Equipment. 2005. National Fire Protection Association.
NFPA 5000: Building and Construction Safety Code. 2006. National Fire Protection Association.
PS1-07: Voluntary Product Standard for Structural Plywood. 2007. American Plywood Association.
PS2-04: Voluntary Product Standard for Wood-based Structural-use Panels. 2004. American Plywood Association.
RESNET: Mortgage Industry National Home Energy Rating System Standards. 2006. Residential Energy Services Network.
SCS-EC-10.2-2007: Scientific Certification Systems (SCS) Indoor Air Quality Performance Environmental Certification Program: Indoor Advantage Gold. 2007. Scientific Certification Systems.
UL 127: Standard for Factory-Built Fireplaces. 1996. Underwriters Laboratories, Inc.
UL 181A: Standard for Closure Systems for Use With Rigid Air Ducts. 2005. Underwriters Laboratories, Inc.
UL 181B: Standard for Closure Systems for Use With Flexible Air Ducts and Air Connectors. 2005. Underwriters Laboratories, Inc.
UL 1482: Standard for Solid-Fuel Type Room Heaters. 1996. Underwriters Laboratories, Inc.
UL 2034: Standard for Single and Multiple Station Carbon Monoxide Alarms. 1996. Underwriters Laboratories, Inc.
WAC 173-433-100 (3): Washington State Code, Chapter 173-433: Solid Fuel Burning Devices, section 100 (3) Emissions performance standards. 1993.
Climate Zones Throughout the Continental United States

Click on the image for a full page, printable version of the map (PDF,
1 page, 296 K, about PDF)
Figure 301.1, 2006 International Energy Conservation Code®
Copyright 2006, Washington, DC: International Code Council. Reproduced
by permission. All rights reserved.
![[logo] US EPA](http://www.epa.gov/epafiles/images/logo_epaseal.gif)

