Jump to main content.


 Waynesville, Illinois (Round 2a)

 
Site Information
Location: Waynesville, IL
Population: 452
Address: 200 E. Second St.
Waynesville, IL 61778
Contact: Loren Huth
309-824-1047
Demonstration Site: 4th and Main
Enclosed Space: None (new building in planning stage)
Source Water: Ground Water (Wells #6 and #8)
Maximum Daily Flow: 70 gpm
Existing Treatment: Chlorination, Fluoridation, and Polyphosphate
Proposed Arsenic
Removal Technology:
Iron Removal
Disposal Option: Sewer

 

Source Water Quality
Analysis Well #6/Well #8
mg/L
Analysis Well #6/Well #8
mg/L
As – Total 0.028/0.035 pH – Units 7.0/7.2
As – Particulate 0.007/.004 Hardness as CaCO3 481/467
As – Soluble 0.021/0.030 Total Alkalinity
as CaCO3
681/NA
Soluble – As (III) 0.017/0.028 Calcium (Ca) 103/98
Soluble – As (V) 0.004/0.002 Magnesium (Mg) 54/54
Iron (Fe) 2.659/2.427 Sodium (Na) 59/49
Manganese (Mn) 0.019/0.021 Chloride (Cl) 7/NA
Total P
(reported as PO4)
0.3/0.04 Fluoride (F) 0.9/NA
Silica (SiO2) 20/NA Vanadium (V) 0.0003/0.0001
Nitrate (NO3 – N) <0.05/NA Total Dissolved Solids (TDS) 338/NA
Sulfate (SO4) <1/NA Total Organic Carbon (TOC) 9/NA
Note: Well water sample collected (12/05/06) and analyzed by Battelle, Columbus, OH.
NA = Not available

Contact

Tom Sorg
513-569-7370


Local Navigation


Jump to main content.