1. Facility Information: Puget Sound Energy Fredonia Generating Station 2. Location: Skagit County, Washington near town of Mt. Vernon. 48ø27'17" N latitude, 122ø26'14"W longitude. 3. Distance from U.S./Canada border: 30 miles 4. Type and Size of Facility: Puget Sound Energy proposes to install two 54 MW simple cycle natural gas-fired Pratt & Whitney FT-8 twin pac turbines at its existing 228 MW power generation peaking facility near Mt. Vernon. No. 2 fuel oil is available as a backup fuel. 5. Source of Emissions: Combustion turbines. 6. Type of fuel: Primary - natural gas, Backup - No. 2 fuel oil. 7. Type and Quantity of Emissions & 8. Emission Control Technology: For two new gas fired combustion turbines (108 MW combined), maximum permitted potential to emit (8760 hours / yr) considering controls: Quantity Quantity of of Emissions Emissions Firing Gas Firing Oil Pollutant (tons / yr) (tons / yr) Emission Control Technology PM10 30 53 Good combustion practices SO2 15 224 Good combustion practices NOx 102 102 Good combustion practices, water injection, & SCR VOC 42 35 Good combustion practices, oxidation catalyst CO 124 124 Good combustion practices, oxidation catalyst H2 SO4 69 69 Good combustion practices HAP 9 9 Good combustion practices, oxidation catalyst 9. Application Received: May 4, 2001, October 5, 2001. 10. Stack height and diameter: Stack 1: Height: 50 feet Diameter: 11 feet Stack 2: Height: 50 feet Diameter: 11 feet 11. Permitting Authority: State of Washington Department of Ecology Air Quality Program Attn: Tapas Das P.O. Box 47600 Olympia, WA 98504-7600 Phone: 360.407.6803 Northwest Air Pollution Authority Attn: Lester Keel 1600 South 2nd Street Mount Vernon, WA 98273-5202 Phone: 360.428.1617, ext 209