1. Name of the facility Detroit Thermal, LLC 2. Location 541 Madison Avenue, Detroit, Michigan 3. Distance from the US/Canada border approximative 5 km 4. Type/size of the facility installation of 3 new package boilers 5. Source of emissions natural gas and/or No 2 oil fired boilers 6. Type of fuel natural gas and/or No 2 oil 7. Type/quantity of emissions NOx: 76.4 lb/hour; 0.036 lb/MMBTU if uses natural gas; 0.140 lb/MMBTU if uses oil CO: 84.6 lb/hour; 0.073 lb/MMBTU if uses natural gas; 0.155 lb/MMBTU if uses oil PM 10: 21.8 lb/hour; 0.007 lb/MMBTU if uses natural gas; 0.04 lb/MMBTU if uses oil SO2: 39 tpy 8. Emission control technology low-NOx burners, state of the art combustion practices, use of natural gas (low sulfur fuel) with a limit of sulfur not higher than 0.3% by weight 9. Date permit application received 03/10/2005 10. Stack height and diameter each stack has a maximum diameter of 120 in, and a minimum height of 250 in. 11.Permit agency's contact name, address, telephone number John Vial Michigan Department of Environmental Quality, Air Quality Division, Constitution Hall 525 West Allegan Street Lansing, MI, 48909 Tel. 517 241 - 7468