Skip to main content
U.S. flag

An official website of the United States government

Here’s how you know

Dot gov

Official websites use .gov
A .gov website belongs to an official government organization in the United States.

HTTPS

Secure .gov websites use HTTPS
A lock (LockA locked padlock) or https:// means you’ve safely connected to the .gov website. Share sensitive information only on official, secure websites.

    • Environmental Topics
    • Air
    • Bed Bugs
    • Chemicals, Toxics, and Pesticide
    • Emergency Response
    • Environmental Information by Location
    • Health
    • Land, Waste, and Cleanup
    • Lead
    • Mold
    • Radon
    • Research
    • Science Topics
    • Water Topics
    • A-Z Topic Index
    • Laws & Regulations
    • By Business Sector
    • By Topic
    • Compliance
    • Enforcement
    • Guidance
    • Laws and Executive Orders
    • Regulations
    • Report a Violation
    • Environmental Violations
    • Fraud, Waste or Abuse
    • About EPA
    • Our Mission and What We Do
    • Headquarters Offices
    • Regional Offices
    • Labs and Research Centers
    • Planning, Budget, and Results
    • Organization Chart
    • EPA History

Breadcrumb

  1. Home
  2. Reducing HFCs

Technology Transitions HFC Restrictions by Sector

EPA Administrator Lee Zeldin signed a final rule titled “Phasedown of Hydrofluorocarbons: Reconsideration of Certain Regulatory Requirements Promulgated Under the Technology Transitions Provisions of the American Innovation and Manufacturing Act of 2020.” This webpage has not yet been updated to reflect that final rule. For updated restrictions, please visit our webpage on Regulatory Actions for Technology Transitions. 

Beginning January 1, 2025, certain technologies may no longer use high global warming potential (GWP) hydrofluorocarbons (HFCs) or HFC blends. Prohibitions apply to the manufacture, distribution, sale, installation, import, and export of products containing restricted HFCs and on the installation of new systems that use restricted HFCs. More information on the sectors and subsectors, regulatory context, and ongoing rulemakings is available on the Technology Transitions Program website.

  • Aerosols – Restricted Products by Sector and Subsector Table
  • Foams – Restricted Products by Sector and Subsector Table
  • Self-contained Refrigeration, Air Conditioning, and Heat Pumps – Restricted Products by Sector and Subsector Table
  • Refrigeration, Air Conditioning, and Heat Pumps – Restricted Systems by Sector and Subsector Table

More information

  • Final Rule Fact Sheet: Restrictions on the Use of HFCs in Certain Sectors (pdf) (946 KB) – Find tables of restricted products for all sectors and subsectors

Aerosols – Restricted Products by Sector and Subsector Table*

SubsectorGlobal Warming Potential Limit or Prohibited SubstancesManufacture and Import Compliance Date1
Consumer aerosol products150January 1, 2025
Technical aerosol products2150January 1, 2028

Foams – Restricted Products by Sector and Subsector Table*

SubsectorGlobal Warming Potential Limit or Prohibited SubstancesManufacture and Import Compliance Date1
Polyurethane3 (rigid, flexible, integral skin, laminated boardstock)150January 1, 2025
Polystyrene extruded boardstock and billet and extruded sheet150January 1, 2025
Phenolic insulation board and bunstock150January 1, 2025
Polyisocyanurate laminated boardstock150January 1, 2025
Polyolefin150January 1, 2025

Self-contained Refrigeration, Air Conditioning, and Heat Pumps – Restricted Products by Sector and Subsector Table*

Sort by

SubsectorProductGlobal Warming Potential Limit or Prohibited SubstancesManufacture and Import Compliance Date1
aStationary residential and light commercial air conditioning and heat pumps (e.g., window units, portable room air conditioning)Stationary residential and light commercial air conditioning and heat pumps (e.g., window units, portable room air conditioning)700January 1, 2025
bResidential dehumidifiersResidential dehumidifiers700January 1, 2025
cHousehold refrigerators and freezersHousehold refrigerators and freezers150January 1, 2025
dVending machinesVending machines150January 1, 2025
eMotor vehicle air conditioningLight-duty passenger vehicles150Model Year 2025, and no earlier than [One year after date of publication in the Federal Register]
fMotor vehicle air conditioningMedium-duty passenger vehicles, heavy-duty pick-up trucks, complete heavy-duty vans150Model Year 2028
gMotor vehicle air conditioningListed nonroad vehicles (agricultural tractors greater than 40 horsepower; self-propelled agricultural machinery; compact equipment; construction, forestry, and mining equipment; and commercial utility vehicles)150January 1, 2028
hChillers (as a stand-alone product)Industrial process refrigeration with exiting fluid below -50 °C (-58 °F)Not coveredNot covered
iChillers (as a stand-alone product)Industrial process refrigeration with exiting fluid greater than or equal to -50 °C (-58 °F) and less than -30 °C (-22 °F)700January 1, 2028
jChillers (as a stand-alone product)Industrial process refrigeration with exiting fluid equal to or above -30 °C (-22 °F)700January 1, 2026
kChillers (as a stand-alone product)Comfort cooling700January 1, 2025
lChillers (as a stand-alone product)Ice rinks700January 1, 2025
mData centers, computer room air conditioning, and information technology equipment coolingData centers, computer room air conditioning, and information technology equipment cooling700January 1, 2027
nIndustrial process refrigeration (not using chillers)With refrigerant entering the evaporator below -50 °C (-58 °F)Not coveredNot covered
oIndustrial process refrigeration (not using chillers)With refrigerant entering the evaporator equal to or above -50 °C (-58 °F) and less than -30 °C (-22 °F)700January 1, 2028
pIndustrial process refrigeration (not using chillers)High temperature side of cascade system and temperature of the refrigerant entering the evaporator equal to or above -30 °C (-22 °F)300January 1, 2026
qIndustrial process refrigeration (not using chillers)With less than 200 lb refrigerant charge and temperature of the refrigerant entering the evaporator equal to or above -30 °C (-22 °F)300January 1, 2026
rIndustrial process refrigeration (not using chillers)With 200 or more lb refrigerant charge excluding high temperature side of cascade system and temperature of the refrigerant entering the evaporator equal to or above -30 °C (-22 °F)150January 1, 2026
sRetail food - refrigeration stand-alone unitsRetail food - refrigeration stand-alone units150January 1, 2025
tRetail food - refrigerated food processing and dispensing equipment500 g of refrigerant or less and outside scope of UL 621, edition 7150January 1, 2027
uRetail food - refrigerated food processing and dispensing equipmentMore than 500 g of refrigerant and outside scope of UL 621, edition 7R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-407H, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-427A, R-428A, R-434A, R-437A, R-438A, R-507A, HFC-134a, HFC-227ea, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, Freeze 12January 1, 2027
vRetail food - refrigerated food processing and dispensing equipmentIce cream makers within the scope of UL 621, edition 7R-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-407H, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-427A, R-428A, R-434A, R-437A, R-438A, R-507A, HFC-134a, HFC-227ea, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, Freeze 12January 1, 2028
wSelf-contained automatic commercial ice machinesBatch type: harvest rate <=1,000 lb ice per 24 hours150January 1, 2026
xSelf-contained automatic commercial ice machinesContinuous type: harvest rate <=1,200 lb ice per 24 hours150January 1, 2026
ySelf-contained automatic commercial ice machinesBatch type: harvest rate above 1,000 lb ice per 24 hoursR-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-442A, R-507, R-507A, HFC-134a, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, G2018C, Freeze 12January 1, 2027
zaSelf-contained automatic commercial ice machinesContinuous type: harvest rate above 1,200 lb ice per 24 hoursR-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-428A, R-434A, R-437A, R-438A, R-442A, R-507, R-507A, HFC-134a, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, G2018C, Freeze 12January 1, 2027
zbCold storage warehousesWith 200 or more lb refrigerant charge, excluding high temperature side of cascade system150January 1, 2026
zcCold storage warehousesWith less than 200 lb refrigerant charge300January 1, 2026
zdCold storage warehousesHigh temperature side of cascade system300January 1, 2026
zeRefrigerated transport4Intermodal containers with refrigerant temperature entering the evaporator below -50 °C (-58 °F)Not coveredNot covered
zfRefrigerated transport4Intermodal containers with refrigerant temperature entering the evaporator equal to or above -50 °C (-58 °F)700January 1, 2025
zgRefrigerated transport4Road—self-contained productsR-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation), GHG-X5January 1, 2025
zhRefrigerated transport4Marine—self-contained productsR-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation), GHG-X5January 1, 2025

Refrigeration, Air Conditioning, and Heat Pumps – Restricted Systems by Sector and Subsector Table*

Sort by

SubsectorSystemGlobal Warming Potential Limit or Prohibited SubstancesInstallation Compliance Date5
aStationary residential and light commercial air conditioning and heat pumps Residential and light commercial air conditioning and heat pump systems (e.g., mini-splits, unitary systems)700January 1, 20266
bStationary air conditioning and heat pumpsVariable refrigerant flow systems700January 1, 20277
cChillersIndustrial process refrigeration with exiting fluid below -50 °C (-58 °F)Not coveredNot covered
dChillersIndustrial process refrigeration with exiting fluid from -50 °C (-58 °F) to -30 °C (-22 °F)700January 1, 2028
eChillersIndustrial process refrigeration with exiting fluid above -30 °C (-22 °F)700January 1, 2026
fChillersComfort cooling700January 1, 2025
gIce rinksIce rinks700January 1, 2025
hData centers, computer room air conditioning, and information technology equipment coolingData centers, computer room air conditioning, and information technology equipment cooling700January 1, 2027
iIndustrial process refrigeration (not using chillers)With 200 or more lb refrigerant charge excluding high temperature side of cascade system and temperature of the refrigerant entering the evaporator above -30 °C (-22 °F)150January 1, 2026
jIndustrial process refrigeration (not using chillers)With less than 200 lb refrigerant charge and temperature of the refrigerant entering the evaporator above -30 °C (-22 °F)300January 1, 2026
kIndustrial process refrigeration (not using chillers)High temperature side of cascade systems and temperature of the refrigerant entering the evaporator above -30 °C (-22 °F)300January 1, 2026
lIndustrial process refrigeration (not using chillers)Temperature of the refrigerant entering the evaporator from -50 °C (-58 °F) to -30 °C (-22 °F)700January 1, 2028
mIndustrial process refrigeration (not using chillers)Temperature of the refrigerant entering the evaporator below -50 °C (-58 °F)Not coveredNot covered
nCold storage warehousesWith 200 or more lb refrigerant charge, excluding high temperature side of cascade system150January 1, 2026
oCold storage warehousesWith less than 200 lb refrigerant charge300January 1, 2026
pCold storage warehousesHigh temperature side of cascade system300January 1, 2026
qRetail food - supermarketsWith 200 or more lb refrigerant charge, excluding high temperature side of cascade system150January 1, 2027
rRetail food - supermarketsWith less than 200 lb refrigerant charge300January 1, 2027
sRetail food - supermarketsHigh temperature side of cascade systems300January 1, 2027
tRetail food - remote condensing unitsWith 200 or more lb refrigerant charge, excluding high temperature side of cascade system150January 1, 2026
uRetail food - remote condensing unitsWith less than 200 lb refrigerant charge300January 1, 2026
vRetail food - remote condensing unitsHigh temperature side of cascade system300January 1, 2026
wRetail food - remote refrigerated food processing and dispensing equipmentRetail food - remote refrigerated food processing and dispensing equipmentR-402A, R-402B, R-404A, R-407A, R-407B, R-407C, R-407F, R-407H, R-408A, R-410A, R-410B, R-411A, R-411B, R-417A, R-417C, R-420A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-426A, R-427A, R-428A, R-434A, R-437A, R-438A, R-507A, HFC-134a, HFC-227ea, R-125/290/134a/600a (55/1/42.5/1.5), RB-276, RS-24 (2002 formulation), RS-44 (2003 formulation), GHG-X5, Freeze 12January 1, 2027
xRemote automatic commercial ice machinesRemote automatic commercial ice machinesR-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation), GHG-X5January 1, 2027
yRefrigerated transportIntermodal containers with exiting fluid temperature from a chiller below -50 °C (-58 °F)Not coveredNot covered
zaRefrigerated transportIntermodal containers with exiting fluid temperature from a chiller equal to or above -50 °C (-58 °F)700January 1, 2025
zbRefrigerated transportRoad systemsR-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation), GHG-X5January 1, 2025
zcRefrigerated transportMarine systemsR-402A, R-402B, R-404A, R-407B, R-408A, R-410B, R-417A, R-421A, R-421B, R-422A, R-422B, R-422C, R-422D, R-424A, R-428A, R-434A, R-438A, R-507A, R-125/290/134a/600a (55/1/42.5/1.5), RS-44 (2003 formulation), GHG-X5January 1, 2025

*Note: this is the Systems table, not Products


*These tables are for informational purposes only and should not be relied on for compliance purposes. Please refer to 40 CFR Part 84, Subpart B for full details.

1. Sale, distribution, and export of these products is prohibited three years after the manufacture and import compliance date.

2. See regulatory text for specific types of aerosol products subject to the later compliance date. Excludes metered dose inhalers using HFC-134a or HFC-227ea or defense sprays using HFC-134a as a propellant.

3. Includes blown foam, products incorporating blown foam, and pre-blended polyol products. Excludes composite structural preformed polyurethane foam for trailer use and for marine use.

4. New products only; does not apply to equipment that is operational during transport.

5. EPA is restricting the installation of new field-assembled systems. Components used to repair existing systems are not subject to these restrictions.

6. New systems with a GWP above 700 can be installed until January 1, 2026, so long as all components are manufactured or imported prior to January 1, 2025 (refer to the Interim Final Rule for additional details).

7. New systems with a GWP above 700 can be installed until January 1, 2027, so long as all components are manufactured or imported prior to January 1, 2026. New systems with a GWP above 700 can be installed until January 1, 2028, in buildings that were issued an approved building permit prior to October 5, 2023, as long as that permit approved the use of an HFC or blend containing an HFC in such a system, and all components used in that system are manufactured or imported prior to January 1, 2026 (refer to the Variable Refrigerant Flow Air Conditioning Final Rule for additional details).

Contact Us About Reducing HFCs to ask a question, provide feedback, or report a problem.
Last updated on May 21, 2026
  • Assistance
  • Spanish
  • Arabic
  • Chinese (simplified)
  • Chinese (traditional)
  • French
  • Haitian Creole
  • Korean
  • Portuguese
  • Russian
  • Tagalog
  • Vietnamese
United States Environmental Protection Agency

Discover.

  • Accessibility Statement
  • Budget & Performance
  • Contracting
  • EPA www Web Snapshot
  • Grants
  • No FEAR Act Data
  • Plain Writing
  • Privacy and Security Notice

Connect.

  • Data
  • Inspector General
  • Jobs
  • Newsroom
  • Regulations.gov
  • Subscribe
  • USA.gov
  • White House

Ask.

  • Contact EPA
  • EPA Disclaimers
  • Hotlines
  • FOIA Requests
  • Frequent Questions
  • Site Feedback

Follow.